![Carrier ZS Plus Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/carrier/zs-plus/zs-plus_installation-manual_2560240024.webp)
SPT Sensors
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
20
Using an SPT Sensor
All SPT Sensors
Feature
Usage
Local Access port
See
To communicate through the Local Access port
(page 11).
SPT Plus
Feature
Usage
Slide potentiometer
Move the potentiometer to raise or lower the zone's setpoint. The maximum you
can adjust the setpoint is defined in the
Max Adjust
field*.
MANUAL ON button
Press this button one time to override the schedule and set the zone to occupied
for the amount of time defined in the
Each pulse
field*. Press the button again to
incrementally increase the time. For example, if the
Each pulse
field is set at five
minutes, press the button once for an occupancy of five minutes, twice for ten
minutes, and so on. The maximum length of time you can override the schedule is
defined in the
Max Accum
field*.
To cancel the override, hold down the
MANUAL ON
button until the
OCCUPIED
LED
turns off.
OCCUPIED LED
The LED lights when the zone is occupied from a regular schedule or a manual
override.
SPT Pro
Feature
Usage
Display
The display shows occupancy, zone temperature, and an alarm bell icon. Celsius
values are to the nearest 0.5 degree; Fahrenheit values are to the nearest full
degree.
The display shows
Occupied
when the zone is occupied from a regular schedule or
from a manual override.
MANUAL ON button
Press one time to override the schedule and set the zone to occupied for the
amount of time defined in the
Each pulse
field*. Press button again to
incrementally increase the time. For example, if the
Each pulse
field is set at five
minutes, press the button once for an occupancy of five minutes, twice for ten
minutes, and so on. The maximum length of time you can override the schedule is
defined in the
Max Accum
field*.
The display shows the duration of the override in minutes. If the override time
exceeds 199 minutes, the display shows the time in hours.
To cancel the override, hold the button down until
0
displays. Wait five seconds for
the display to show the current zone temperature again.
Downloaded from