![Carrier ZS Plus Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/carrier/zs-plus/zs-plus_installation-manual_2560240016.webp)
ZS Sensors
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
12
Troubleshooting
ZS Pro or ZS Pro-F
If display shows...
Then...
Incorrect or missing
values
Check for errors in the i-Vu® application and Snap.
On the control program's
Properties
page, select the
Rnet Points
tab. Verify that
values coming in from the sensors and those going out to the sensors are expected
values.
In the i-Vu® application, double-click the Sensor Binder and ASVI microblocks to
check for problems in the
Status
and/or
Error
columns.
If the
Error
column shows
Resource Allocation
, try formatting the sensor. If the error is
not corrected by formatting, the control program engineer should reduce the number
of items that the sensor is trying to display.
Nothing
The sensor has no power.
The sensor is not communicating with the network. Check:
•
Software/addressing setup
•
Wiring connections
•
Controller operating status
Characters that
seem out
of place
The sensor may have a memory problem. Try formatting the sensor.