![Carrier ZS Plus Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/carrier/zs-plus/zs-plus_installation-manual_2560240032.webp)
Alternate space temperature sensor
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
28
To change a T59 sensor's options
You can change user options and field service options in the T59's display. The options are displayed on pages
referenced by page number. See tables below.
NOTE
Because the T-59 is not a communicating device, the T-59's setpoint and offset values must be set to
match the same values in the associated controller.
To display an
option page
1
In the User Options and Field Service Options tables below, find the option you
want to change and its page number.
2
With the sensor displaying the current temperature, simultaneously press and hold
the
and
keys. After 30 seconds, the sensor's display shows option page
100
.
3
Release the keys.
4
Press
repeatedly until the display shows the page number you want.
NOTE
To display a field service option page (
126
to
132
), press the
key until
you see
1- -
, then simultaneously press and hold
and
. After
approximately 2 seconds, the display shows
126
. Press
until you see the
page you want.
NOTE
If you do not press a key for 30 seconds, the sensor automatically returns to
normal operation.
To edit a value
1
When the option page you want is displayed, press
to enter edit mode.
2
Press
repeatedly to cycle through the numbers
00
to
12
. Stop at the number
that represents the value you want. See tables below.
3
Press
to save the selected value and return to option page.
NOTE
If you do not press a key for 10 seconds, the sensor automatically returns to
option page.
To return sensor to
normal operation
From an option page, press
until the display shows
1- -
. Then press
.
Downloaded from