Alternate space temperature sensor
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
27
To wire and mount the sensor
1
Turn the 2 setscrews at the bottom of the sensor clockwise to release the sensor's cover from the mounting
plate.
2
Lift the cover from the bottom, and then release it from the top fasteners.
3
Feed the wires from the electrical box through the opening in the center of the sensor mounting plate.
4
Use the 2 mounting screws provided to attach the mounting plate to the electrical box.
5
Strip the outer jacket from the cable for at least 3 inches (7.62 cm). Strip .25 inch (.6 cm) of insulation from
each wire. Cut the shield and drain wire from the cable.
6
Use the appropriate diagram below to connect the wiring to the sensor's terminals.
7
Reattach the sensor's cover to the mounting plate, inserting the top first.
8
Turn the two Allen screws counterclockwise to secure the cover to the mounting plate.
9
Wire the sensor to the Open controller. See the controller's
Installation and Startup Guide
for details.
NOTE
Clean sensor with damp cloth only. Do not use solvents.
T-55 sensor
T-56 sensor
T-59 sensor
Red
Blk (Gnd)
White
Jumper
terminals
SENSET
SEN
Blk (Gnd)
Sens or
wiring
Red
Sens or
wiring
Blu
Blk
Brn
Sens or
wiring
PWR
+
COM
-
OPB
Downloaded from