Relative Humidity sensors
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
53
Wiring specifications
Cable from sensor to controller:
If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length:
500 feet (152 meters)
Mounting location
Mount this sensor...
In this location
Space RH sensor
•
On an interior wall
•
Approximately 5 feet (1.5 meters) from the floor, beside the space temperature
sensor
•
At least 4 feet (1.2 meters) from any corner. Reduced airflow in corners results
in erratic sensor readings.
•
Vertically so that the Carrier logo is correctly oriented
Do not mount the sensor:
•
In drafty areas such as near heating or air-conditioning ducts, open windows, or
fans
•
Over heat sources such as baseboard heaters, radiators, or wall-mounted light
dimmers
•
In areas of excessive moisture, corrosive fumes, or vibration
Sensors mounted in these areas will produce inaccurate readings.
NOTE
The sensor mounting plate accommodates the NEMA standard 2x4 in.
standard single gang electrical box. However, the sensor can be mounted directly on
the wall surface if local codes permit.
Duct RH sensor
The zone's return air duct
Outdoor RH sensor
Where the sensor is protected from the elements and direct sunlight, such as under
an eave