background image

38

Low Ambient Cooling Operation Down to 45°F (7°C)

In Low Ambient RTU conditions when the temperature is be-

tween 55°F (13°C) and 45°F (7°C), the Low Ambient Switch

(LAS) will be active and the outdoor-fans will run to the pre-set

factory outdoor-fan speed. When the temperature is greater than

65°F (18°C), the Low Ambient Switch will deactivate and the out-

door-fans will run in the standard cooling mode. If the Outdoor

Fan Select Switch (see Fig. 52) is in the up position, the outdoor

fans will run in the Fan Cycle Speed Mode (FCS) set to 250 rpm.

If the Outdoor Fan Select Switch is in the down position, the out-

door fans will run in the Minimum Fan Speed Mode (MIN) set to

160 rpm regardless of the cooling demand.
At temperatures below 45°F (7°C), unit will utilize economizer

for SA temperature control.
48LC Size 14 through 26 Units have a SPST normally open Low

Ambient Switch wired across the TS and OF terminal and a jump-

er placed across the PS terminal (see Fig. 53). When the LAS is

active, the switch will close making contact to the OF terminal.

This is done for units that require all outdoor fans to run at the

same pre-set factory low ambient speed.
Table 9 shows the operation of the outdoor fan for each unit.

Fig. 52 — Outdoor Fan Speed Select Switch

Fig. 53 — Schematic of SPST Low Ambient Switch

Heating

In the Heating Mode (W1 and G), the ISC board sends power to

W on the IGC board. The indoor-fan motor will energize and the

outdoor-air dampers will open to their minimum position. The

ISC board upon seeing W1 and G ON will turn the indoor fan to

high speed.
The IGC board starts its gas ignition process. A check is made to

ensure that the rollout switch and limit switch are closed. If the

check was successful, the induced draft motor is energized, and

when its speed is satisfactory, as proven by the “hall effect” sensor,

the ignition activation period begins. The burners will ignite with-

in 5 seconds. If the burners do not light, there is a 22 second delay

before another 5 second attempt. This sequence is repeated for

15 minutes or until the burners light. If, after the 15 minutes, the

burners still have not lit, heating is locked out. To reset the control,

break 24VAC power to the VAV-RTU Open.
When gas ignition occurs, the IGC board will continue to monitor

the condition of the rollout switch, the limit switches, the “hall ef-

fect” sensor, as well as the flame sensor.
When W1 is turned OFF, the IGC board turns off the gas valve.

The IGC board has a delay time before it turns IFO=OFF. At this

time, the ISC board sees W1=OFF and IFO=ON. The ISC will

keep the indoor fan ON high speed. Once the IGC board delay

times out, the ISC board will see W1=OFF and IFO=OFF, which

then turns the indoor fan OFF.
If the call for W1 lasted less than 1 minute, the heating cycle will

not terminate until 1 minute after W1 became active. The indoor

fan motor will continue to operate for an additional 45 seconds

then stop. If the overtemperature limit opens after the indoor mo-

tor is stopped, but within 10 minutes of W1 becoming inactive, on

the next cycle the time will be extended by 15 seconds. The maxi-

mum delay is 3 minutes. Once modified, the fan OFF delay will

not change back to 45 seconds unless power is reset to the control.

A LED indicator is provided on the IGC to monitor operation.
When additional heat is required, W2 closes and initiates power to

the second stage of the main gas valve. When the zones are satis-

fied, the gas valve closes, interrupting the flow of gas to the main

burners.

Morning Warm-up

The control will provide a Morning Warm-up cycle the first time

if transition from unoccupied to occupied and if the heating is re-

quired and the unit goes into heating immediately. Whenever the

unit enters the heating mode, before any heat stage is enabled,

the control will provide a Linkage mode to the system that will

cause the terminals to maintain sufficient airflow. The Linkage

mode of Warm-up (2) will be sent to the terminal system to in-

sure sufficient airflow while in the heating mode but also provid-

ing a controlled warm-up cycle to prevent overheating of some

zones. As a safety measure, should the heating cycle continue

and the SAT approach the “Maximum Heating SAT” limit, the

Linkage mode sent will change to Pressurization (6) to insure all

terminals open to their maximum airflow. The Linkage mode

will remain Pressurization until that heating cycle ends. Once the

heating demand is met and the heat cycle is completed or if cool-

ing is required, heating will be locked out until the beginning of

the next occupied period.

Occupied Heating

Optionally, the user may enable occupied heating which will allow

heating whenever heating is needed during the occupied period.

The cycle will operate exactly the same as Morning Warm-up

above, except it will not be limited by the transition into an occu-

pied period.

Table 9 — Low Ambient Temperature Outdoor Fan 

Control

48LC

UNIT

NO. OF

FANS ON

NO. OF

FANS OFF

SWITCH

OUTDOOR

FAN SELECT

SWITCH

RPM

14

3

0

SPST

Up

250

17

4

0

SPST

Up

250

20

4

0

SPST

Up

250

24

6

0

SPST

Up

250

26

6

0

SPST

Up

250

OF SPEED

SELECT

ON

FCS

MIN

OFF

JUMPER ON

LAS

SPST

PS

PS

TS

OF

Содержание WeatherExpert 48LC B14 Series

Страница 1: ...ing of air conditioning equipment can be hazardous due to system pressure and electrical components Only trained and qualified service personnel should install repair or service air conditioning equipment Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters All other operations should be performed by trained service personnel When working ...

Страница 2: ...s le bâtiment Vérifier que toutes les ouvertures pratiquées dans le mur ex térieur autour du ou des tuyaux d évent et de la prise d air sont scellées de manière à empêcher l infiltration de produits de combustion dans le bâtiment Veiller à ce que la ou les sorties de l évent de l appareil de chauffage et la prise d air ne soient en aucune façon ob struées quelle que soit la saison GAS VALVE INLET ...

Страница 3: ...Guard N Precoat Al Cu Al Cu Louvered Hail Guard P E coat Al Cu Al Cu Louvered Hail Guard Q E coat Al Cu E coat Al Cu Louvered Hail Guard R Cu Cu Al Cu Louvered Hail Guard S Cu Cu Cu Cu Louvered Hail Guard Voltage 1 575 3 60 5 208 230 3 60 6 460 3 60 Design Revision Factory Design Revision Intake Exhaust Options required on each unit B Temperature Low Leak Economizer with Barometric Relief C Temper...

Страница 4: ...4 Fig 2 48LC B14 Vertical Airflow ...

Страница 5: ...5 Fig 3 48LC B14 Horizontal Airflow ...

Страница 6: ...6 Fig 4 48LC B14 Back View and Condensate Drain Location ...

Страница 7: ...7 Fig 5 48LC B14 Corner Weights and Clearances ...

Страница 8: ...8 Fig 6 48LC B14 Bottom View ...

Страница 9: ...9 Fig 7 48LC B17 20 Vertical Airflow ...

Страница 10: ...10 Fig 8 48LC B17 20 Horizontal Airflow ...

Страница 11: ...11 Fig 9 48LC B17 20 Back View and Condensate Drain Location ...

Страница 12: ...12 Fig 10 48LC B17 20 Corner Weights and Clearances ...

Страница 13: ...13 Fig 11 48LC B17 20 Bottom View ...

Страница 14: ...14 Fig 12 48LC B24 26 Vertical Airflow ...

Страница 15: ...15 Fig 13 48LC B24 26 Horizontal Airflow ...

Страница 16: ...16 Fig 14 48LC B24 26 Back View and Condensate Drain Location ...

Страница 17: ...17 Fig 15 48LC B24 26 Corner Weights and Clearances ...

Страница 18: ...18 Fig 16 48LC B24 26 Bottom View ...

Страница 19: ... Refer to Step 11 Install External Condensate Trap and Line for re quired trap dimensions ROOF MOUNT Check building codes for weight distribution requirements Unit operating weight is shown in Table 2 Step 2 Plan for Sequence of Unit Installation The support method used for this unit will dictate different se quences for the steps of unit installation For example on curb mounted units some accesso...

Страница 20: ...ontal airflow units see Fig 3 8 or 13 Attach the service connections to the basepan SLAB MOUNT HORIZONTAL UNITS ONLY Provide a level concrete slab that extends a minimum of 6 in 150 mm beyond unit cabinet Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstruct ing airflow NOTE Horizontal units may be installed on a roof curb if required ALTERNATE UNIT...

Страница 21: ...21 Fig 20 48LC B14 Roof Curb Details ...

Страница 22: ...22 Fig 21 48LC B17 20 Roof Curb Details ...

Страница 23: ...23 Fig 22 48LC B24 26 Roof Curb Details ...

Страница 24: ...s and sizes of the horizontal duct connections Note that there are two different return air duct connection locations one for non VAV units without an economizer on back side of unit and a different one for LC B VAV units with the integrated economizer on left end under the economizer hood The sup ply air duct connection is on the back side See Fig 23 for top view depicting typical horizontal duct...

Страница 25: ...ons 1 Remove hood top panel from shipping position on unit end 2 Install filters supports item 1 to the upper end panel using the screws provided 3 Install each deflector item 8 on to each filter support item 1 using the screws provided 4 Apply seal strip to mating flanges on side plates of hood items 4 and 5 5 Secure side panels items 4 and 5 to upper panel using the screws provided 6 Apply seal ...

Страница 26: ... the hood to the back of the burner access panel Using the two screws re attach the hood to the front of the burner access panel as shown in Fig 31 Fig 31 Flue Hood and Combustion Air Hood Details Step 12 Install Gas Piping Installation of the gas piping must be in accordance with local building codes and with applicable national codes In U S A refer to NFPA 54 ANSI Z223 1 National Fuel Gas Code N...

Страница 27: ...han 13 in wg 3240 Pa at the unit connection see Table 5 Manifold pressure is factory adjusted for NG fuel use Adjust as required to obtain best flame characteristics See Table 6 Manifold pressure for LP fuel must be adjusted to specified range see Table 7 Follow instructions in the accessory kit to make ini tial readjustment Table 3 Typical 3 4 in NPT Field Supplied Piping Parts ITEM QTY DESCRIPTI...

Страница 28: ...damage Support all piping with appropriate straps hangers etc Use a minimum of one hanger every 6 ft 1 8 m For pipe sizes larger than 1 2 in follow recommen dations of national codes 3 Apply joint compound pipe dope sparingly and only to male threads of joint when making pipe connections Use only pipe dope that is resistant to action of liquefied petro leum gases as specified by local and or natio...

Страница 29: ...nnect On a unit without a unit mounted disconnect or HACR connect the source leads to the terminal block with unit field power leads See Fig 38 Fig 38 Location of TB1 Field power wires are connected to the unit at line side pressure lugs on the terminal block see wiring diagram label for control box component arrangement or at factory installed option non fused disconnect switch or HACR breaker Us...

Страница 30: ...30 Fig 40 48LC B14 26 VAV RTU Open Control Wiring Diagram ...

Страница 31: ...31 Fig 41 48LC B14 26 Power Wiring Diagram ...

Страница 32: ... silver metal collar is at OFF 3 Insert the shaft with the cross pin on the top of the shaft in the horizontal position 4 Measure the tip of the shaft to the outside surface of the cor ner post to be 0 88 in 5 Tighten the locking screw to secure the shaft to the NFD 6 Turn the handle to OFF position with red arrow pointing at OFF 7 Install the handle on to the corner post vertically with the red a...

Страница 33: ...atherproof Cover Aweatherproof while in use cover for the factory installed conve nience outlets is now required by UL standards This cover cannot be factory mounted due to its depth it must be installed at unit in stallation For shipment the convenience outlet is covered with a blank cover plate The weatherproof cover kit is shipped in the unit s control box The kit includes the hinged cover a ba...

Страница 34: ...and power line phasing if the GFCI receptacle does not trip as required Press the RESET button to clear the tripped condition Using unit mounted convenience outlets Units with unit mounted convenience outlet circuits will often re quire that two disconnects be opened to de energize all power to the unit Treat all units as electrically energized until the conve nience outlet power is also checked a...

Страница 35: ... KIT Correctly rated low voltage wire can be routed through the rubber grommet located on the corner post adjacent to the control box ac cess panel Route wire through the grommet and then route the wire behind the corner post utilizing the factory provided wire ties secured to the control box This will insure separation of the field low voltage wire and the high voltage circuit Route the low volt ...

Страница 36: ...en LED Note 1 2 Check HPS LPS COFS RED RED 3 Call for Y3 with no call for Y1 Check Y1 wiring RED 4 Call for Y3 with no call for Y1 Y2 Check Y1 wiring RED RED 5 Call for Y2 with no call for Y1 Check Y1 wiring RED RED 6 Call for W2 with no call for W1 Check W1 wiring RED RED 7 Call for heat W1 W2 and cooling Y1 Y2 Y3 Check VAV RTU Open wiring RED RED RED RED 8 Call for heat W1 W2 with no IFM Check G...

Страница 37: ...l be cal culated based on the output of the DCV calculation Two user con figurable values are provided the DCV Max Ctrl Setpoint is the differential CO2 setpoint that is used as the control point and a DCV Max Vent Damper Pos provides the ability to limit the maximum amount of outdoor air being introduced into the unit through the economizer by the DCV control The economizer will be positioned at ...

Страница 38: ... time before it turns IFO OFF At this time the ISC board sees W1 OFF and IFO ON The ISC will keep the indoor fan ON high speed Once the IGC board delay times out the ISC board will see W1 OFF and IFO OFF which then turns the indoor fan OFF If the call for W1 lasted less than 1 minute the heating cycle will not terminate until 1 minute after W1 became active The indoor fan motor will continue to op...

Страница 39: ...ation The Open VAV terminals will recognize the Heating or Warm up modes as a heat mode and uti lize the higher airflow minimum setpoint as configured The sys tem will further monitor the SAT of the RTU to determine if the SAT is approaching the configured maximum limit As the limit is approached the Linkage mode is changed to Linkage Pressuriza tion to ensure all terminals open to their maximum s...

Страница 40: ...eter value 3 Setup number shows the active setup and the edit setup If the same set up acts as both the active and edit set up only that setup number is shown factory setting When the active and edit setup differ both numbers are shown in the display SETUP 12 The flashing number indicates the edit setup 4 The symbol in the number 4 position in the figure above indicates motor direction The arrow p...

Страница 41: ...e requires use of the VFD Keypad which is included as part of the field installed Multi Speed VFD display kit PN CRDISKIT002A00 If the VFD keypad is not already installed install it See Connecting the Keypad to the VFD for details To program the VFD for variable indoor fan motor speeds 1 At Power Up At the first power up the LCD displays the Select Language screen The default setting is English se...

Страница 42: ...Menu The display shows the following b Press OK twice the display changes to c Press Down Arrow three times to reach the fol lowing display d Press OK to highlight the number in the bracket and then use the and Up and Down Arrow keys to select the desired voltage and Hertz for the unit e Press OK to accept the selection and continue 5 Entering Motor Data a Press the Menu key to move the triangle i...

Страница 43: ...provided in Tables 10 14 Press OK again to set the selected value g Press Down Arrow twice the following display appears h Press OK to highlight the number in the bracket and then use the and Up and Down Arrow keys to select the number provided in Tables 10 14 Press OK again to set the selected value i Press the Back key once the following display appears j Press Down Arrow once the following disp...

Страница 44: ...ollowing display appears f Press Down Arrow again the following display appears NOTE Press OK to highlight the Hz value and then use the and Up and Down Arrow keys to enter the required values g Press Down Arrow once the following display appears NOTE Press OK to highlight the value and then use the and Up and Down Arrow keys to enter the required value See Tables 10 14 for proper selection of the...

Страница 45: ...ighlight the number in the bracket g Use the and Up and Down Arrow keys to change the number to 3 for 3 automatic resets and then press OK The display changes to h Press Down Arrow once the following display appears i Press OK to highlight the number of seconds and use the and Up and Down Arrow keys to select 600 seconds Press OK again to set the selected value j Press the Back key once the follow...

Страница 46: ...T REFERENCE Motor Option Voltage 1 71 1 73 1 82 1 90 3 10 0 3 10 1 3 10 2 3 10 3 3 10 4 3 10 5 3 10 6 3 10 7 STD 208 230 2 0 1 1 0 4 0 53 43 79 57 100 100 0 0 0 460 2 0 1 1 0 4 0 53 43 79 57 100 100 0 0 0 575 2 0 1 1 0 4 0 53 43 79 57 100 100 0 0 0 MID 208 230 2 0 1 1 0 4 0 53 43 79 57 100 100 0 0 0 460 2 0 1 1 0 4 0 53 43 79 57 100 100 0 0 0 575 2 0 1 1 0 4 0 53 43 79 57 100 100 0 0 0 HIGH 208 23...

Страница 47: ...0 21 2 1760 460 HD60FK657 HK30WA380 131L9867 1 122 14 460 60 9 7 1760 575 HD60FL576 HK30WA384 131N0229 1 132 14 575 60 7 2 1745 HIGH 208 230 HD62FK654 HK30WA374 131L9799 1 102 15 230 60 28 0 1760 460 HD62FK654 HK30WA381 131L9868 1 122 15 460 60 13 7 1760 575 HD62FL576 HK30WA384 131N0229 1 132 15 575 60 8 9 1750 ULTRA 208 230 HD64FK654 HK30WA375 131L9800 1 102 16 230 60 37 3 1755 460 HD64FK654 HK30...

Страница 48: ...0 60 3 600 0 575 2 10 0 60 3 600 0 HIGH 208 230 2 10 0 60 3 600 0 460 2 10 0 60 3 600 0 575 2 10 0 60 3 600 0 ULTRA 208 230 2 10 0 60 3 600 0 460 2 10 0 60 3 600 0 575 2 10 0 60 3 600 0 Table 12 VFD Unit Parameters 48LC B Size 20 REGIONAL SETTINGS GRID TYPE MOTOR POWER MOTOR VOLTAGE MOTOR FREQUENCY Hz MOTOR CURRENT MUST HOLD AMPS MOTOR NOMINAL SPEED RPM Motor Option Voltage Motor P N VFD Carrier P...

Страница 49: ...INAL 18 DIGITAL INPUT TERMINAL 19 DIGITAL INPUT TERMINAL 27 DIGITAL INPUT TERMINAL 29 DIGITAL INPUT Motor Option Voltage 3 41 3 42 4 18 5 10 5 11 5 12 5 13 STD 208 230 10 00 10 00 100 8 16 17 18 460 10 00 10 00 100 8 16 17 18 575 10 00 10 00 100 8 16 17 18 MID 208 230 10 00 10 00 100 8 16 17 18 460 10 00 10 00 100 8 16 17 18 575 10 00 10 00 100 8 16 17 18 HIGH 208 230 10 00 10 00 100 8 16 17 18 46...

Страница 50: ... 33 64 48 100 100 0 0 0 575 2 0 1 1 0 4 0 52 33 64 48 100 100 0 0 0 MID 208 230 2 0 1 1 0 4 0 52 33 64 48 100 100 0 0 0 460 2 0 1 1 0 4 0 52 33 64 48 100 100 0 0 0 575 2 0 1 1 0 4 0 52 33 64 48 100 100 0 0 0 HIGH 208 230 2 0 1 1 0 4 0 52 33 64 48 100 100 0 0 0 460 2 0 1 1 0 4 0 52 33 64 48 100 100 0 0 0 575 2 0 1 1 0 4 0 52 33 64 48 100 100 0 0 0 RAMP UP TIME sec RAMP DOWN TIME sec CURRENT LIMIT T...

Страница 51: ... 00 72 00 100 100 0 0 0 575 2 0 1 1 0 4 0 60 00 72 00 100 100 0 0 0 MID 208 230 2 0 1 1 0 4 0 60 00 72 00 100 100 0 0 0 460 2 0 1 1 0 4 0 60 00 72 00 100 100 0 0 0 575 2 0 1 1 0 4 0 60 00 72 00 100 100 0 0 0 HIGH 208 230 2 0 1 1 0 4 0 60 00 72 00 100 100 0 0 0 460 2 0 1 1 0 4 0 60 00 72 00 100 100 0 0 0 575 2 0 1 1 0 4 0 60 00 72 00 100 100 0 0 0 RAMP UP TIME sec RAMP DOWN TIME sec CURRENT LIMIT T...

Страница 52: ... hand partition 3 Orient the tube s sampling holes into the return air flow direc tion For vertical application position the sampling holes on the bottom of the tube facing into the bottom return duct opening For horizontal application position the sampling holes on the side of the tube facing the unit s end panel 4 Insert the sampling tube into the return air sensor module until the tube snaps in...

Страница 53: ......

Страница 54: ... discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480267 01 Printed in U S A Form 48LCB 14 26 02SI Pg 54 9 19 Replaces 48LCB 14 26 01SI 2019 Carrier Corporation ...

Страница 55: ...d range Y N _____ Check gas piping for leaks Y N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y N _____ Verify that unit is level Y N _____ Check fan wheels and propeller for location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are properly tensioned Y N _____ Verif...

Страница 56: ...LINE PRESSURES Gas Inlet Pressure _____________IN WG Gas Manifold Pressure STAGE 1 _____________IN WG STAGE 2 _____________IN WG Refrigerant Suction CIRCUIT A _____________ PSIG CIRCUIT B _____________ PSIG Refrigerant Discharge CIRCUIT A _____________ PSIG CIRCUIT B _____________ PSIG Verify Refrigerant Charge using Charging Charts Y N _____ GENERAL Economizer minimum vent and changeover settings...

Отзывы: