Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3
-E2
CARRIER CORPORATION ©2022
Installation and Start-up Guide
All rights reserved
136
Point Name/Description
Default/Range
Sensor Array:
Sensor calculation method -
When using multiple SPT sensors, select the process
variable to be passed to the controller..
D:
R:
Avg
Avg, Min, Max
BACnet configuration:
Network Visible -
Must be enabled for other BACnet objects to read or write to this
point, and for this point to generate alarms.
D:
Enabled
Object Name -
Do not change.
D: zone_temp
CO2 Sensor
–
The current voltage of the controller's
IN-01
input.
R: 0 to 5 Vdc
Flow Control / Flow Input
- The current value of the controller's flow sensor input.
R: 0 to 99999 cfm
(liters/second)
RH Sensor
–
The current voltage of the controller's
IN-01
input.
R: 0 to 5 Vdc
T55 Zone Temp
–
The current value of the controller's
IN-02
space temperature sensor
input.
R: -56 to 245°F
(-48.9 to 118.3°C)
SAT Sensor
–
The current value of the controller's
IN-03
supply air temperature sensor
input.
R: -56 to 140°F
(-48.9 to 60°C)
Hot Wtr Vlv 1 Stat
–
The value provided by the controller's Smart Valve.
R: _%
LUX
–
The value provided by the controller's ZS sensor to indicate lighting level.
R: 0 to 1020 lx
WS Battery Strength %
—
Displays charge strength indicated on the wireless space
temperature sensor. If there are multiple wireless sensors, it displays the lowest value.
R: _%
WS Signal Strength %
—
Displays radio signal strength of the wireless space
temperature sensor. If there are multiple wireless sensors, it displays the lowest value.
R: _%
Zone Humidity
–
The value provided by the controller's ZS or wireless sensor (if
present). See details below.
R: _%
Zone Temp
–
The value provided by the controller's ZS or wireless sensor (if present).
R: _F°
ZS Zone CO2 -
IAQ/CO2 signal received from
CO2-enabled ZS Sensor(s).
R: _ppm