Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3
-E2
CARRIER CORPORATION ©2022
Installation and Start-up Guide
All rights reserved
107
NOTE
Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.
Status
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Status
Point Name/Description
Range
Terminal Mode
–
The controller's current operating status.
R: Off
Heating
Warm-up
Vent
Cooling
Dehumidify
Reheat
Pressurize
Evacuate
Shutdown
IAQ Override
Air Balancing
Terminal Type
–
The type of zone terminal that the controller is installed on.
R: Single Duct
Parallel Fan
Series Fan
Space Temperature
- Prime Variable
–
The space temperature value currently used for
control.
R: -56 to 245°F
(-48.9 to 118.3°C)
Primary Airflow
–
The current airflow measured through the primary air damper.
R: 0 to 99999 cfm
(liters/second)
Damper Position
–
The current damper position.
R: 0 to 100%
Supply Air Temperature
–
Displays the current supply air temperature.
R: -56 to 245°F
(-48.9 to 118.3°C)
Heating Capacity
–
The current reheat capacity when the zone is configured for reheat.
R: 0 to 100%
Baseboard Heating Capacity
–
The current baseboard heat capacity when the zone is
configured for Combination Baseboard or Non-ducted Heat.
R: 0 to 100%
Outdoor Air Temperature
–
The current outdoor air temperature from a linked air
source, if available, or from another network source.
R: -56 to 245°F
(-48.9 to 118.3°C)
Appendix A: TV-VAVB3-E2 Points/Properties