To communicate through the BACnet/Service port network
TruVu™ VAVB3
-E2
CARRIER CORPORATION ©2022
Installation and Start-up Guide
All rights reserved
95
13
Click
Apply
.
14
On the right of the page, in the
Networks using selected connection
table, click the checkbox next to the
network you want to connect to.
15
Click
Apply
.
16
Select the
BACnet/IP Service Port Connection
and click
Start
. The status changes to
Connected
.
17
Click
Accept
.
18
On the navigation tree, right-click the controller that you are connected to and select
Module Status
. If a
Modstat report appears, the i-Vu® application is communicating with the controller.
Wiring specifications
For...
Use...
Maximum Length
Ethernet - not
daisy chained
Cat5e or higher Ethernet cable
328 feet (100 meters)
Ethernet - a
daisy chain
configuration
Cat5e or higher Ethernet cable
164 feet (50 meters)
MS/TP *
22 AWG, low-capacitance, twisted, stranded,
shielded copper wire
2000 feet (610 meters)
* See the
MS/TP Networking and Wiring Technical Instructions
.
WARNINGS
•
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
•
Do not exceed the minimum bend radius of the Cat5e or Cat6e Ethernet cable. Refer to Ethernet cable
manufacturer specifications for minimum bend radius.