Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3
-E2
CARRIER CORPORATION ©2022
Installation and Start-up Guide
All rights reserved
109
Point Name/Description
Default/Range
DCV Max Vent Airflow
–
The maximum airflow allowed when the IAQ function overrides
the temperature control. When active, the damper modulates to the temperature
control requirement or the
DCV Max Vent Airflow
, whichever is greater. This value is a
percentage of the
Maximum Cooling Airflow Setpoint
.
D:
R:
70%
0 to 100%
Filter Service Alarm Timer
–
Fan type terminals only. The amount of time the fan will
run before generating a
Filter Alarm
. Set to 0 to disable the alarm.
D:
R:
0 hr
0 to 9999 hr
T55 Pushbutton Override
–
Enables or disables the use of a pushbutton override from a
local space temperature sensor.
D:
R:
Enable
Disable/Enable
Setpoint Adjustment
–
Enables or disables the setpoint adjustment mechanism on the
local space sensor.
D:
R:
Enable
Disable/Enable
Setpoint Adjustment Range
- The maximum amount that a user can adjust the setpoint
on the local ZS or SPT sensor.
D: 2 °F (1.1 °C)
Heating Lockout Temperature
–
Supplemental reheat is disabled if outside air
temperature exceeds this value. Supplemental reheat is enabled when the outside air
temperature falls below a fixed hysteresis of 2 °F (1.1 °C). This function is active only
if there is a valid network outside air temperature.
D:
R:
70°F (21.1°C)
35 to 150°F
(1.6 to 65.5°C)
Power Fail Restart Delay
–
How long the controller delays normal operation after the
power is restored. This is typically used to prevent excessive demand when recovering
from a power failure. Applies to Series Fan start delay when system mode transitions
from unoccupied to occupied. A delay of no greater than 120 seconds is recommended
for Series Fan applications.
D:
R:
60 seconds
0 to 600 seconds
Occupancy Schedules
–
If
Enabled
, the controller stores and follows a schedule sent
over the network or programmed locally through a touchscreen or Field Assistant. If
Disabled
, the controller occupancy is controlled from the
BAS On/Off
or
System
Occupancy
network point.
D:
R:
Enable
Disable/Enable
Occ Override Delay
–
The amount of time the controller remains occupied after the
remote occupancy switch returns to the unoccupied position.
D:
R:
15 minutes
0 to 240 minutes