Troubleshooting
TruVu™ VAVB3
-E2
CARRIER CORPORATION ©2022
Installation and Start-up Guide
All rights reserved
101
To configure custom Prog 1/2 LEDs
You can customize the
Prog 1
and/or
Prog 2
LED for site-specific purposes by configuring the BACnet Analog
Output (BAO) microblock.
Open your control program in the Snap interface, select the AO microblock for each LED, and use the following
settings:
Status/Attribute
Microblock
type
Expander number :
Channel number
I/O type
Description
LED 1
BAO
0:61
Special
•
<=0 Normal
•
>15 On
The number of blinks equals the
Present Value.
The pulse pattern repeats after a
2-second delay
LED will blink the number of
times given in the BAO with ON
pulse 0.5 seconds and OFF pulse
0.5 seconds.
LED 2
BAO
0:62
Special
•
<=0 Normal
•
>15 On
The number of blinks equals the
Present Value.
The pulse pattern repeats after a
2-second delay
LED will blink the number of
times given in the BAO with ON
pulse 0.5 seconds and OFF pulse
0.5 seconds.
To get a Module Status report
A Module Status report provides information about the controller and verifies proper network communication with
the controller. You can get this report:
•
In the i-Vu® application
—
Right-click the controller on the navigation tree, then select
Module Status
.
•
In the Field Assistant application
—
Right-click the controller in the navigation tree and select
Module Status
.
•
On the controller setup
ModStat
tab
—
See
To set up the controller through the Service Port
(page 88).
See
Module Status field descriptions
(page 145) in the Appendix.