What is the TV-UCXP683T-V?
TruVu™ UCXP683T
-V
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
3
Power
24 Vac ±15%, 50
–
60 Hz, 55 VA
24 Vdc ±10%, 20 W
NOTE
The above power consumption is for the controller only. Adding devices to
the Act Net bus increases total power consumed.
Eth0, Eth1
10/100 BaseT, full duplex, Ethernet ports for BACnet/IP and/or BACnet/Ethernet
communication.
Under normal operation, network traffic not destined for this controller is repeated
to the other Ethernet port. When the controller is powered off, all traffic received on
one port is mirrored to the other port.
Port S1
For communication with either of the following:
•
A BACnet MS/TP network at 9.6 to 115.2 kbps
•
A Modbus serial network at 9.6 to 115.2 kbps
This port's
End of Net?
switch can be set to
Yes
to terminate the network segment.
I/O Bus
For communication with future expanders.
Rnet port
•
Supports up to 5 wireless and/or ZS sensors, and one Equipment Touch or
TruVu™ ET Display
•
Supplies 12 Vdc/260 mA power to the Rnet across its rated temperature
range.
NOTE Ambient temperature and power source fluctuations exceeding the
listed operating ranges may reduce the power supplied by the Rnet port.
NOTE
If the total power required by the sensors on the Rnet exceeds the
power supplied by the Rnet port, use an external power source. The Wireless
Adapter, Equipment Touch, or TruVu™ ET Display must be powered by an
external power source. See the specifications in each device's Installation and
Start-up Guide to determine the power required.
Act Net port
Supports a combination of up to 5 Act Net addresses, as follows:
•
Address
1
is reserved for the Carrier actuator
•
Address
2
and
3
are reserved for the VAV Zone II Secondary Duct
•
Address
4
and
5
for i-Vu® Smart Valves
Maximum power available for Act Net devices:
•
AC supply - 25 VA (1 A)
•
DC supply - 15W (0.625A)
•
Use an external transformer if your devices exceed the maximum power.
Service port
USB 2.0 host port for setting up the controller and troubleshooting through a local
connection to a computer, c
onnecting to the TruVu™ ET Display, or the Carrier
wireless service adapter.
Comm port
For future use.
Universal inputs
8
Inputs are configurable in the control program for 0
–
5 Vdc, 0
–
10 Vdc, thermistor,
dry contact, or pulse counter.
Input resolution
12 bit A/D
Input pulse frequency
10 pulses per second. Minimum pulse width (on or off time) required for each
pulse is 50 msec.