Adjusting the TV-UCXP683T-V driver properties
TruVu™ UCXP683T
-V
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
38
Notification Classes
A BACnet alarm's Notification Class defines:
•
Alarm priority for Alarm, Fault, and Return to Normal states
•
Options for BACnet alarm acknowledgment
•
Where alarms should be sent (recipients)
Alarms in the i-Vu® application use Notification Class #1. The i-Vu® application is automatically a recipient of
these alarms.
Priorities
NOTE
BACnet defines the following Network message priorities for Alarms and
Events.
Priority range
Network message priority
00
–
63
Life Safety
64
–
127
Critical Equipment
128
–
191
Urgent
192
–
255
Normal
Priority of Off-Normal
BACnet priority for Alarms.
Priority of Fault
BACnet priority for Fault messages.
Priority of Normal
BACnet priority for Return-to-normal messages.
Ack Required for Off-Normal,
Fault, and Normal
Specifies whether alarms associated with this Notification Class require a BACnet
Acknowledgment for Off-Normal, Fault, or Normal alarms.
TIP
You can require operator acknowledgment for an Alarm or Return-to-
normal message (stored in the i-Vu® database). In the i-Vu® interface on the
Alarm
>
Enable/Disable
tab, change the acknowledgment settings for an alarm
source or an alarm category.
Recipient List
Recipients
The first row in this list is from the i-Vu® application. Do not delete this row. Click
Add
if you want other BACnet devices to receive alarms associated with this
Notification Class.
NOTE
Additional entries in this table may be lost after a download.
Recipient Description
Name that appears in the
Recipients
table.
Recipient Type
Use
Address
(static binding) for either of the following:
•
Third-party BACnet device recipients that do not support dynamic binding
•
When you want alarms to be broadcast (you must uncheck
Issue Confirmed
Notifications
). This use is rare.
Days and times
The days and times during which the recipient will receive alarms.
Recipient Device Object
Identifier
Type the
Device Instance
from SiteBuilder (or from the network administrator for
third-party devices) in the
#
field.
Process Identifier
Change for third-party devices that use a BACnet Process Identifier other than 1.
The i-Vu® application processes alarms for any 32-bit Process Identifier.
Issue Confirmed
Notifications
Select to have a device continue sending an alarm message until it receives
delivery confirmation from the recipient.
Transitions to Send
Uncheck the types of alarms you do not want the recipient to get.