Adjusting the TV-UCXP683T-V driver properties
TruVu™ UCXP683T
-V
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
40
Specific Events
On these pages, you can enable/disable, change BACnet alarm properties, or set delays for the following BACnet
alarms:
Specific alarms:
•
Flow Control Alarm
•
Reheat Valve Alarm
NOTE
To set up alarm actions for controller generated alarms, see
Alarms
in i-Vu® Help.
Controller Generated Alarm
Description
Short message shown on the i-Vu®
Alarms
page or in an alarm action when this
type of alarm is generated.
Events
Alarm Category and Alarm
Template
See
Alarms
in i-Vu® Help.
Enable
Clear these checkboxes to disable Alarm or Return to normal messages of this
type from this controller.
Notification Class
Do not change this field.
Custom Translation Tables
Applies to the analog input of an attached expander.
You can set up a translation table that an analog input will use to translate the raw data from a non-linear sensor
to the engineering units you want it to provide on the output wire of the Analog Input microblock. In the navigation
tree, select
Custom Translation Table #1
,
#2
, or
#3
. The
Properties
page has instructions.
For the input to use the translation table, go to the control program's
Properties
page >
I/O Points
tab. Click the
analog input in the
Name
column. On the
Details
tab, set
Sensor Type (Scaling Method)
to
Non-Linear, Custom
Table #__
.