Appendix A - Common HVAC SNVT's
LonWorks Integration Guide
CARRIER CORPORATION ©2018
i-Vu® Link and Open Link
All rights reserved
16
SNVT #
SNVT Name
Element #
Measurement
Value
15
month
0 — 12, 0=not specified
16
day
0 — 31, 0=not specified
17
hour
0 — 23, 0=not specified
18
minute
0 — 59, 0=not specified
18
second
0 — 59, 0=not specified
20
millisecond
0 — 999, 0=not specified
21 — 24
alarm_limit
0 — 255, 0=not specified
95
SNVT_switch
0
value
0 — 100%
1
state
0 = off,
1 = on,
–1 = undefined
103
SNVT_hvac_emerg
0
enumerated
0 = normal
1 = emergency pressurize
2 = emergency depressurize
3 = emergency purge
4 = emergency shutdown
5 = emergency fire
106
SNVT_temp_setpt
0
°C occupied cool
-273.17 — 327.66
1
°C standby cool
-273.17 — 327.66
2
°C unoccupied cool
-273.17 — 327.66
3
°C occupied heat
-273.17 — 327.66
4
°C standby heat
-273.17 — 327.66
5
°C unoccupied heat
-273.17 — 327.66
108
SNVT_hvac_mode
0
enumerated
0 = auto
1 = heat
2 = morning warmup
3 = cool
4 = night purge
5 = pre cool
6 = off
7 = test
8 = emerg heat
9 = fan only
10 = free cooling
11 = ice
12 = max heat
13 = economy
14 = dehumidify
15 = calibrate
16 = emerg cool
17 = emerg steam
18 = max cool
19 = hvac load
20 = no load
109
SNVT_occupancy
0
status
0 = oc–occupied
1 = oc–unoccupied
2 = oc–bypass
3 = oc–standby
oc–nul 0xFF