5 Set up the driver properties
LonWorks Integration Guide
CARRIER CORPORATION ©2018
i-Vu® Link and Open Link
All rights reserved
10
1
On the i-Vu® or Field Assistant navigation tree, right-click on your third party controller.
2
Select
Driver Properties.
3
Expand
Protocols
and select
LonWorks.
4
Select the i-Vu® Link/Open Link Port S2 that connects to the SLTA-10.
5
In the
Baud
field, type 57600, the baud rate that you set on the SLTA-10 DIP switches.
6
Leave the default settings in the remaining fields under
Port Configuration
and the fields under
LonWorks
Protocol Setup
.
7
Under
SLTA Domain Table
, select
Yes
in the
Define Domain Table
field.
8
On the first line of the table (Index
0
), enter appropriate values in each field. See table below.
9
In Windows Notepad, open the .log file that NodeUtil created. To see this file, in the Notepad
Open
dialog box,
select
All Files
in the
Files of type:
field.
Field
Notes
Domain Length
Locate this number in the .log file. The Domain Length is in the
Size
field highlighted in the following example.
Domain ID
Locate this number in the .log file. The Domain ID is 1
2-character segment, 3 segments, or 6 segments. In the following
example, the highlighted Domain ID is 1 2-character segment.
In the i-Vu® or Field Assistant interface, type
-00 a
fter the ID as
many times as needed so that the
Domain ID
field has 6 2-
character sections.
Subnet ID
Locate this number in the .log file. The Subnet ID is highlighted in
the following example.
5 Set up the driver properties