5 Set up the driver properties
LonWorks Integration Guide
CARRIER CORPORATION ©2018
i-Vu® Link and Open Link
All rights reserved
11
Field
Notes
Node ID
In this field, you are giving the SLTA/Router or Link an ID number on
the LonWorks network. Type any value in the range 1–127, but it
cannot
be the same as the Node ID of any LonLonWorks device on
the LonLonWorks network. 99 is typically a good number to use.
Authentication Key
Do not change these values for most applications.
The i-Vu® or Field Assistant application uses this authentication
code if the third-party device requests authentication.
10
Click the
Apply
to refresh the page. Verify the following values in the
SLTA Node Status
section:
○
SLTA Comm Established
: Yes
(SLTA-10 and Carrier controller are communicating.)
○
SLTA Node Online
: Yes
(SLTA-10 and LonWorks network are communicating.)
○
SLTA Node Configured
: Yes
(SLTA-10 has been commissioned.)
○
Address Domain
: (As displayed in the SLTA Domain Table)
11
On the navigation
tree, select
Protocols
.
12
In the
Protocol Status
table, verify that the LonWorks protocol shows
Running
on Port S2.
If the status shows
Not running
or the wrong port, verify port selection and DIP switch settings for that port on the
controller.