3 Configure LonWorks points using the LonWorks Integration Tool
LonWorks Integration Guide
CARRIER CORPORATION ©2018
i-Vu® Link and Open Link
All rights reserved
7
○
The wizard will display a table of NV's. On the row for the SNVT element you want to read from or write to,
click the Microblock Name field to select the microblock that will do the reading or writing. For example,
to read nvoSpaceTemp (SNVT105, element 0), select the ANI you named Space Temp in your control
program.
○
To command a switch SNVT (SNVT 95), use a BNO microblock to write to element 1 of the SNVT.