6 Verify the controller is set up correctly
LonWorks Integration Guide
CARRIER CORPORATION ©2018
i-Vu® Link and Open Link
All rights reserved
13
•
To capture data receipts, after
diagport>
, type:
modbus rx
Press
Enter
.
•
To capture data transmissions, after
diagport>
, type:
modbus tx
Press
Enter
.
•
To capture more detailed diagnostic messages, after
diagport>
, type:
modbus vmsg
Press
Enter
.
•
To capture error messages, after
diagport>
, type:
modbus emsg
Press
Enter
.
13
Verify the displayed text shows:
lonworks reporting level status:
rx on
tx on
flush off
fc1 off
fc2 off
vmsg on
emsg on
off
If
rx
,
tx
,
vmsg
,
or
emsg
show
off
, repeat the appropriate step (13, 14, 15, or 16) to turn on capture
of that item.
14
After
diagport>
, type:
go
Press
Enter
.
15
Run the capture for one of the following periods of time:
•
If all microblock refresh times are one minute or less, run the capture for 5 minutes.
•
If any microblock refresh time is longer than 1 minute, run the capture for 5 times the longest microblock
refresh time.
16
Type:
stop
Press
Enter
. Verify that you see diagport> before doing the next step.
17
After
diagport>
, type:
logout
Press
Enter
.
18
To end the PuTTY session, click the X in the upper right corner.
19
In i-Vu® or Field Assistant, clear the
Enable Telnet diagnostics
checkbox (see steps 3 and 4), then click
OK
.
20
Open the text file from the location you selected in step 11, and then verify that it legibly shows the same
information that PuTTY displayed.