Operating i-Vu CCN Pro
26
i-Vu CCN Pro 4.2
To add expansion equipment for additional groups and zones controlled by your TSM (expansion
controllers)
1
Click
Main Menu
button
, then select
System Setup
.
2
In the navigation tree, right-click the area where you want to place the equipment. Select
Add Equipment
from the drop-down menu or click
in the toolbar.
3
Enter a
Display Name
.
4
Click
CCN Device
and enter the Bus and Element number of the associated TSM. This allows the new
equipment to inherit the tables from that TSM.
NOTE
You cannot change the association once you have clicked
Apply
. To change it, you have to delete
the equipment and start over.
5
Click
Apply
, then
Close
.
6
Exit
System Setup
.
Configure the path to the source of the point for TSM Groups and Zones
A generic list of points is created in i-Vu CCN Pro when the TSM Group or Zone is scanned in to the system or
when you upload the equipment file.
You must initially revise the address of the path for every point!
1
Select the TSM Group or Zone in the navigation tree, then click
Properties
>
Network Points
tab.
2
To substitute the correct Group or Zone number where the double X (XX) is in each path, click the
Search/Replace
button under the
Address
column.
3
Enter "XX" in the
Search
field and enter the appropriate Zone or Group number in the
Replace
field. This
will update all of the paths for that Zone or Group.
IMPORTANT!
TSM Zone 1
requires an extra step because one point has a slightly different name than in Zones 2 thru 64.
The setpoint offset point in Zone 1 is inadvertently named
STPOFF
, while it is named
SPTOFF
in the remaining
Zones.
This will cause an error because the point is incorrectly mapped in the template for Zone 1, even though it is
correctly mapped for Zones 2 through 64.
You must change
SPTOFF
to
STPOFF
for this one zone!
Example:
CCN://LINK/TZDSP01/SPTOFFST
must be changed to
CCN://LINK/TZDSP01/STPOFFST
.