Operating i-Vu CCN Pro
i-Vu CCN Pro 4.2
25
equipment file contains points that you will finish formatting in i-Vu CCN Pro after uploading it.
The user specifies the air source(s) that the TSM will communicate with by configuring its linkage function. A
system can consist either of one TSM communicating with 1 to 4 air sources, or of 1 to 4 TSMs
communicating with a single air source.
1
Start ApplicationBuilder. (Windows
Start
>
All Programs
>
iVu Tools 4.2
)
2
Click
Create Equipment
.
3
Select your equipment type:
○
TSM II Plus Group
○
TSM II Plus Zone
○
TSM II Group
○
TSM II Zone
4
Click
Next
.
5
Type a name for the custom equipment (i.e., Hot Water system) next to
Equipment Name
.
6
Enable
English
or
Metric
units.
7
Click
Next
8
Browse to the desired location to store your equipment file and click the
Save
button.
9
Click
Exit
or
Start Over
to create another equipment file.
Custom graphic
Use ViewBuilder to edit the graphic that is produced the equipment is created in ApplicationBuilder, or make
a custom graphic.
Assign and download a TSM equipment file in i-Vu CCN Pro
When you scan equipment into i-Vu CCN Pro, each TSM will be discovered with Group 1. You must add a new
and separate equipment for each additional zone and group for which a graphic is desired, create the
equipment file for each one in ApplicationBuilder, and then upload the equipment and view file to the new
equipment that was added in i-Vu CCN Pro.
The Group or Zone that you create in ApplicationBuilder contains setpoint support, schedules, and the points
configuration of a Group or Zone. The CCN path information is automatically configured. The automatic path
configuration is incomplete and you must use a Search and Replace function to exchange the generic Groups
or Zones for your specific Group or Zone number.
To upload an equipment file to a TSM group or zone that has already been scanned in or added to i-Vu
CCN Pro
1
In the i-Vu CCN Pro navigation tree, right-click on the equipment and select
Configure
from the drop-
down menu.
Enter the following information in the dialog box:
2
Under
Equipment
, click
Add
. A dialog window will appear.
3
Browse to the .equipment file that was generated in ApplicationBuilder.
4
Click
Continue
. When message appears "File uploaded successfully", click
Close.
5
Click
Close
again.
NOTE
If the
Graphics
tab is highlighted, a message indicating that a "Download is in progress will