Operating i-Vu CCN Pro
20
i-Vu CCN Pro 4.2
1
Start
ApplicationBuilder
. (Windows
Start
>
All Programs
>
iVu Tools 4.2
)
2
Click
Create Equipment
.
3
Select equipment type:
Custom Equipment
>
Link Integration Values to CCN.
4
Click
Next
.
5
Type a name for the custom equipment (i.e., Hot Water system) next to
Equipment Name
.
6
Enable
English
or
Metric
units.
7
Select options from the drop down menus.
8
Click
Next.
9
Choose the type of element, quantity and click the
.
Add Elements to your application
NOTE
Elements
are a collection of input/output points that perform a specific operation. The
input/output point that is reading or writing to the UC/CC is called a CCN point.
The available Elements that you can add to your custom equipment in ApplicationBuilder are:
Point type
Used for
Read CCN Point
Reading an analog or binary value from the UC/CC
Carrier Text Point
Read a text string from the UC/CC
Analog - Setpoint Write
Reading and writing individual variables
Analog - Link CCN to Integration
Writes CCN variables to TPI
Analog – Link Integration to CCN
Writes TPI variables to CCN
Analog – Link CCN Passive to Integration
Writes CCN variables to TPI
Analog – Link Integration to CCN Passive
Writes TPI variables to CCN
Analog – BACnet to CCN
Writes BACnet variable to CCN
Binary – Link CCN to Integration
Writes CCN variables to TPI
Binary – Link Integration to CCN
Writes TPI variables to CCN
Binary – Link CCN Passive to Integration
Writes CCN variables to TPI
Binary – Link Integration to CCN Passive
Writes TPI variables to CCN
Binary – BACnet to CCN
Writes BACnet variable to CCN
1
As you add Elements, enter the requested information for the CCN or TPI points:
○
Display Text -
the description of the point as it will appear in i-Vu CCN Pro (i.e., Pump status)
○
Reference Base -
the name of the point which will be used when linking the point to a graphic
element. All points have a unique identifier (i.e.,input_pumpstat, trendPumpstat)