42
20. TEST RUNNING
20.1 NOTES
-
Operate testing running after completion of connecting refrigerant piping lines,
drain line and electrical wiring and refrigerant leak test.
-
Operate test running after mounting air filters, and front panel of indoor unit.
20.2 STEPS FOR COOLING TEST RUNNING
a.
Move circuit breaker to ON position.
b.
Operate the system for cooling operation
at high fan speed by using wireless remote control.
c.
After system operation becomes stabilized:
-
Measure low pressure to check correct
refrigerant charge. (See figure & table )
-
Measure total Amps consumed by the system.
-
Measure System working voltage.
System Cooling Test Running
SYSTEM MODEL
53QC36-708
53QC48-508
AMBIENT TEMP ºC
35
35
LOW PRESSURE PSI
71 62
TOTAL AMPS
18.5
8.3
NOTE
Readings at 220 volt and 27 ºC return air to indoor unit and high speed of indoor unit motor.
Readings at 380 volt and 27 ºC return air to indoor unit and high speed of indoor unit motor.
20.3 STEPS FOR HEATING TEST RUNNING
a.
Move circuit breaker to ON position.
b.
Operate the system for heating operation
at high fan speed by using wireless remote control.
c.
After system operation becomes stabilized:
-
Measure high pressure to check correct
refrigerant charge. (See figure)
-
Measure total Amps consumed by the system.
-
Measure system-working voltage.
System Heating Test Running
SYSTEM MODEL
53QC36-708
53QC48-508
AMBIENT TEMP ºC
7
7
HIGH PRESSURE PSI
225
240
TOTAL AMPS
16
8.1
NOTE
Readings at 220 volt and 27 ºC return air to indoor unit and high speed of indoor unit motor.
Readings at 380 volt and 27 ºC return air to indoor unit and high speed of indoor unit motor.
1. High Pressure Measuring.
(1)
Outdoor Unit
Details
1. Low Pressure Measuring.
(1)
Outdoor Unit
Details