40
CONNECTING ELECTRICAL WIRING (Cont.)
18-7 FIELD ELECTRICAL CONNECTIONS FOR SYSTEM 53QC48-508
LEGEND
Earth
L1, L2, L3 Live power supply.
N Neutral
N1 Neutral connection indoor / outdoor unit
A1 Live connection indoor/outdoor unit.
4 Voltage control
O Reversing Valve Control
W2 Outdoor Fan Control
Y Compressor control
Sizes of electrical wires
L1
L2
L3
N
N1-N
A1-L
4
O
W2
Y
4 mm
2
4 mm
2
1 mm
2
1 mm
2
1 mm
2
1 mm
2
1 mm
2
1 mm
2
1 mm
2
1 mm
2
IMPORTANT NOTE
Control connection cable between outdoor and indoor units
This cable is factory supplied of length 6 meter.
This cable must be field connected to PCB of outdoor unit at connector ( CN305 ) and must be
also field connected to PCB of indoor unit.
In case of requesting this cable of length more than 6 meter, an additional cable with connector
must be purchased from Carrier.
The two cables of 6 meter each must be connected together at field and connected to both
outdoor and indoor units.
NOTES
(1)
Connect the power supply to the outdoor unit and then get the power required
for the indoor unit from the outdoor unit.
(2)
All dotted lines to be fitted by installer.
(3)
Refer to wiring diagrams and stickers-caution sticked inside the outdoor & indoor units.
OUTDOOR UNIT
TERMINAL BLOCKS
INDOOR UNIT
TERMINAL BLOCKS
Main Switch
Circuit breaker
SUPPLY POWER
380-420/3/50
INDOOR
PCB
OUTDOOR
PCB