CONNECTING REFRIGERANT PIPING LINES (Cont.)
16.3 USE OF REFRIGERANT PIPING LINES
The following data refers to the use of refrigerant piping lines of diameters equivalent to that use in
units where : L = Maximum length of refrigerant piping lines between outdoor and indoor units.
H = Maximum vertical distance between outdoor and indoor units.
(A)
OUTDOOR UNIT BELOW INDOOR UNIT :
Slop tubing towards the outdoor unit with a fall of at least (6mm) to (305mm).
(B)
OUTDOOR UNIT ABOVE INDOOR UNIT :
•
If height is less than or equal 4 meters, one oil trap must be at the gas line at the base of gas
riser near the Indoor unit to facilitate oil return to the compressor to ensure efficiency of
compressor mechanical parts.
•
If height is more than 4 meters, more than one oil trap must exist at the gas line, the first one
will be at the gas line near to the indoor unit and the following one will be 4 meters from the
first one and so on.
(C)
OUTDOOR UNIT ON THE SAME LEVEL AS INDOOR UNIT:
An oil trap is preferred to be at the gas line at the base of gas riser near the Indoor unit to
facilitate oil return to the compressor to ensure efficiency of compressor mechanical parts.
Outdoor
Unit
Outdoor
Unit
Indoor Unit
Indoor
Unit
Outdoor
Unit
Indoor Unit
Oil Trap
Liquid
Gas
System
Model
Meters
L
H
53QC36 25 10
53QC48 30 15
System
Model
Meters
L
53QC36 25
53QC48 30
System
Model
Meters
L
H
53QC36 25 10
53QC48 30 15