38
CONNECTING ELECTRICAL WIRING (Cont.)
18-3 ELECTRICAL DATA
Split
System
Model
Starting
Current
(Note 1)
System
Power
Supply
Electrical Consumption
Main Power
Connections
Cooling
Heating
***
Circuit
Breaker
Wire
Size
(Note 2)
35 °C
*
46 °C
**
Heat Pump
Amp
V/Ph/Hz
Amp
Watt
Amp
Watt
Amp
Watt
Amp mm²
53QC36-708
110 220-240/1/50 18.3 3825 21.2 4594 15 3024 40 6
53QC48-508
65 380-420/3/50 8.3 3980 9.6 4775 8.1 3860 20 4
NOTES
1. Starting Current duration is usually less than 1 Second.
2. Wire size shown applies to standard applications with line length up to 25 meter for model 53QC36
and 30 meter for model 53QC48.
3. Operating Conditions.
*
Standard operating conditions in standard ambient for cooling
Indoor 27/19 °C DBT/WBT Outdoor 35 °C DBT High speed of indoor unit motor
**
Maximum operating conditions in standard ambient for cooling
Indoor 27/19 °C DBT/WBT Outdoor 46 °C DBT High speed of indoor unit motor
*** Standard
operating
conditions for heating
Indoor 20 °C DBT Outdoor 7/6 °C DBT/WBT High speed of indoor unit motor
18-4 CONNECTING ELECTRICAL WIRING TO OUTDOOR UNIT
Connect electrical cables to the terminal block of outdoor
unit as per the wiring diagram and caution – field wiring.
(1)
Avoid slack connections of electrical cables
with the terminal block.
(2)
Avoid miswiring of electrical cables
connections with the terminal block.
WARNING
!