CONNECTING ELECTRICAL WIRING (Cont.)
18-6 FIELD ELECTRICAL CONNECTIONS FOR SYSTEM 53QC36-708
LEGEND
Earth
N Neutral power supply
L Live Power Supply
C Neutral connection indoor/outdoor unit.
R Live connection indoor/outdoor unit
Y Compressor
control.
O Reversing valve control
W Outdoor fan motor control
T3 Outdoor coil sensor
Sizes of electrical wires
N
L
C
R
Y
O
W2
6 mm
2
6 mm
2
1 mm
2
1 mm
2
1 mm
2
1 mm
2
1 mm
2
IMPORTANT NOTE
Cable of outdoor coil sensor between outdoor and indoor units
This cable is factory supplied of length 6 meter.
This cable must be field connected to PCB of outdoor unit and must be also field connected to
PCB of indoor unit at connect (CN1)
In case of requesting this cable of length more than 6 meter, an additional cable with connector
must be purchased from Carrier.
The two cables of 6 meter each must be connected together at field and connected to both
outdoor and indoor units.
NOTES (1) Connect the power supply to the outdoor unit and then get the power
required for the indoor unit from the outdoor unit.
(2) All dotted lines to be fitted by installer.
(3) Refer to wiring diagrams and stickers-caution sticked inside the outdoor & indoor units.