24
30XBEZE from 900 to 1200
30XBEZE
900
950
1050
1150
1200
Power circuit supply
Nominal voltage
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1)
Standard unit
kW
Circuit 1
(a)
kW
154
163
224
245
262
Circuit 2
(a)
kW
246
262
244
260
262
Option 081
kW
399
426
468
505
524
Unit + option 15LS
Circuit 1
(a)
kW
147
157
215
236
253
Circuit 2
(a)
kW
236
253
235
252
253
Option 081
kW
383
410
450
487
505
Power factor at maximum power
(1)
Standard unit
Displacement Power Factor (Cos Phi)
0,89
0,89
0,89
0,89
0,89
Unit + option 15LS
Displacement Power Factor (Cos Phi)
0,89
0,89
0,89
0,89
0,89
Nominal operating current draw
(2)
Standard unit
Circuit 1
(a)
A
174
184
250
267
292
Circuit 2
(a)
A
270
292
267
288
292
Option 081
A
444
475
516
555
583
Unit + option 15LS
Circuit 1
(a)
A
163
173
235
252
275
Circuit 2
(a)
A
253
275
252
273
275
Option 081
A
416
447
486
524
549
Maximum operating current draw (Un)
(1)
Standard unit
Circuit 1
(a)
A
250
265
365
397
425
Circuit 2
(a)
A
400
425
397
422
425
Option 081
A
650
690
762
819
850
Unit + option 15LS
Circuit 1
(a)
A
240
255
351
383
410
Circuit 2
(a)
A
384
410
383
408
410
Option 081
A
624
665
733
790
819
Maximum current (Un-10%)
(1)
Standard unit
Circuit 1
(a)
A
269
285
392
426
457
Circuit 2
(a)
A
429
457
426
454
457
Option 081
A
697
741
818
879
913
Unit + option 15LS
Circuit 1
(a)
A
259
275
378
412
441
Circuit 2
(a)
A
414
441
412
440
441
Option 081
A
672
716
790
851
882
Nominal start-up current
(3)
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Option 081
A
854
876
893
915
918
Option 081 & Opt 25c
A
629
640
672
683
683
Maximum start-up current(Un)
(2)
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Option 081
A
987
1012
1026
1051
1054
Option 081 & Opt 25c
A
761
776
804
819
818
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B..
4 -PHYSICAL AND ELECTRICAL DATA FOR 30XB(E/P)ZE UNITS