26
30XBPZE from 900 to 1200
30XBPZE
900
950
1050
1150
1200
Power circuit supply
Nominal voltage
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1)
Standard unit
kW
Circuit 1
(a)
kW
154
164
222
243
260
Circuit 2
(a)
kW
244
262
242
258
260
Option 081
kW
397
425
464
501
520
Unit + option 15LS
Circuit 1
(a)
kW
151
162
219
240
256
Circuit 2
(a)
kW
240
258
239
255
256
Option 081
kW
391
419
457
494
513
Power factor at maximum power
(1)
Standard unit
Displacement Power Factor (Cos Phi)
0,88
0,89
0,88
0,89
0,89
Unit + option 15LS
Displacement Power Factor (Cos Phi)
0,88
0,89
0,88
0,89
0,89
Nominal operating current draw
(2)
- 30XBPZE
Standard unit
Circuit 1
(a)
A
173
183
245
263
287
Circuit 2
(a)
A
265
289
263
284
287
Option 081
A
438
472
507
546
573
Unit + option 15LS
Circuit 1
(a)
A
169
179
240
257
281
Circuit 2
(a)
A
260
283
257
279
281
Option 081
A
428
462
497
536
561
Maximum operating current draw (Un)
(1)
Standard unit
Circuit 1
(a)
A
252
267
363
395
423
Circuit 2
(a)
A
398
426
395
420
423
Option 081
A
649
692
758
815
846
Unit + option 15LS
Circuit 1
(a)
A
247
263
358
390
417
Circuit 2
(a)
A
392
420
390
415
417
Option 081
A
639
682
747
804
834
Maximum current (Un-10%)
(1)
Standard unit
Circuit 1
(a)
A
270
286
390
424
454
Circuit 2
(a)
A
427
457
424
452
454
Option 081
A
697
743
814
876
908
Unit + option 15LS
Circuit 1
(a)
A
266
282
385
419
449
Circuit 2
(a)
A
421
451
419
447
449
Option 081
A
687
733
804
865
897
Nominal start-up current
(3)
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Option 081
A
852
876
892
913
916
Option 081 & Opt 25c
A
627
640
670
681
680
Maximum start-up current(Un)
(2)
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Option 081
A
985
1013
1024
1049
1052
Option 081 & Opt 25c
A
759
777
802
817
816
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B.
4 -PHYSICAL AND ELECTRICAL DATA FOR 30XB(E/P)ZE UNITS