53
According to regulation No. 327/2011 implementing directive 2009/125/EC with regard to eco-design requirements for fans
driven by motors with an electric input power between 125 W and 500 kW.
30XB(E/P)ZE
30XBEZE
30XBPZE
Overall efficiency
%
40,1
47,3
Measurement category
A
A
Afficiency category
static
static
Target effciency level ERP2015
N(2015) 40
N(2015) 40
Effciency level at optimum efficiency point
44,6
52,2
Variable speed drive
YES
YES (embedded)
year of manufacture
See label on the unit
See label on the unit
Fan manufacturer
Simonin
Simonin
Motor manufacturer
Leroy Somer
EBM Papst
Fan PN
00PSG002630700A
00PSG002630700
Motor PN
00PPG000558700A
00PSG002696800A
Nominal power of the motor
kW
1,96
1,68
Flow rate
m
3
/s
4,22
4,24
Pressure at optimum energy efficiency
Pa
174,2
174,6
Nominal speed
rpm
948
959
specifica ratio
1,002
1,002
Relevant information to facilitate the disassembly, recycling or
removal of the product at the end of life
See the maintenance manual
See the maintenance manual
Relevant information to minimise theimpact on the environment
See the maintenance manual
See the maintenance manual
Regulation 2019/1781 repealing 640/2009, governs the requirements relating to ecodesign applicable to electric motors and
to speed regulators in accordance with the directive 2009/125/EC.
30XB(E/P)ZE
30XBEZE
30XBPZE
Number of poles
6
6
Nominal input frequency
Hz
50
50/60
Nominal voltage
V
400
380/480
Number of phases
3
3
Motor included in the application domain of the regulation 2019/1781
No
NO
Rationale for exemption
Article 2,1
Article 2,1
Ambient air temperature for which the motor is specifically designed
°C
70
70
Above data for fans and motors, which are mandatory regarding eco-design regulation, are provided for a stand-alone component (not
included in the chiller system).
11.6 - Electronic expansion valve (EXV)
The EXV is equipped with a stepper motor (2785 to 3690 steps,
depending on the model) that is controlled via the EXV board. The
EXV is also equipped with a sightglass that permits verification of
the mechanism movement and the presence of the liquid gasket.
11.7 - Moisture indicator
Located on the EXV, permits control of the unit charge and indicates
moisture in the circuit. The presence of bubbles in the sight-glass
indicates an insufficient charge or non-con-densables in the
system. The presence of moisture changes the colour of the
indicator paper in the sight-glass.
11.8 - Filter drier
The role of the filter drier is to keep the circuit clean and moisture-
free. The moisture indicator shows, when it is necessary to change
the element. A difference in temperature between the filter inlet
and outlet shows that the element is dirty.
11.9 - Sensors
The units use thermistors to measure the temperature, and
pressure transducers to control and regulate system operation.
Refer to the SmartVu
TM
control manual for a more detailed
explanation.
11.10 - Service valve (option 92)
The unit can be equipped with optional service valves to facilitate
maintenance and repair operations.
If option 92 is ordered, each refrigerant circuit will be supplied with
shut-off valves on the compressor economiser, discharge and
suction lines.
ATTENTION: The compressor suction valve must be used
without pressure difference at the terminals. If there is a
pressure difference, leak-tightness at the valve may be lost
and the valve can even fail altogether.
Equal pressure
11 -MAJOR SYSTEM COMPONENTS AND OPERATION DATA