27
4.5 - Compressor electrical data
Compressor
I Nom
(1)
I Max
(Un)
(2)
I Max
(Un - 10%)
(3)
LRYA
A
(4)
LRDA
A
(5)
Cos
Phi nom.
(6)
Cos
Phi Max.
(7)
06TSA155
48
69
74
170
530
0,87
0,90
06TSA186
57
82
89
170
530
0,86
0,89
06TTA266
87
135
146
303
945
0,86
0,90
06TTA301
98
152
164
388
1210
0,87
0,90
06TTA356
115
174
188
388
1210
0,87
0,90
06TUA483
151
229
248
587
1828
0,87
0,88
06TUA554
161
244
264
587
1828
0,88
0,89
06TVA680
218
336
362
629
1919
0,87
0,88
06TVA753
235
367
397
629
1919
0,88
0,89
06TVA819
256
393
424
629
1919
0,88
0,89
Legend
(1) Nominal current draw at standard Eurovent conditions (see definition of conditions under nominal unit current draw)
(2) Maximum operating current
(3) Maximum compressor operating current, limited by the unit (current given for maximum capacity at 360 V)
(4) Locked rotor current for star connection (connection during compressor start-up)
(5) Locked rotor current for delta connection
(6) Value at standard Eurovent conditions: evaporator entering/leaving water temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C.
(7) Value at maximum capacity and nominal voltage
4.6 - Compressor usage per circuit (A, B)
Compresseur
Circuit 200 230 250 300 350 400 450 500 550 600 630 700 750 900 950 1050 1150 1200
06TSA155
A
1
B
1
1
1
06TSA186
A
1
1
1
B
1
1
06TTA266
A
1
B
06TTA301
A
1
B
1
1
06TTA356
A
1
1
1
B
1
1
1
06TUA483
A
1
1
1
1
B
1
06TUA554
A
1
1
1
B
1
06TVA680
A
1
B
06TVA753
A
1
B
1
1
06TVA819
A
1
B
1
1
1
4 -PHYSICAL AND ELECTRICAL DATA FOR 30XB(E/P)ZE UNITS