14
3.9 - Multiple chiller installation
It is recommended to install multiple chillers in a single row, arranged as shown in the example below, to avoid recycling of warm air
from one unit to another.
1.5 m
mini
1,5 m
mini
If the situation at the site does not permit this arrangement, contact your Carrier distributor to evaluate the various possible arrangements.
In certain situations an accessory (supplied loose at the time of purchase) can be added.
3.10 -
Distance to the wall
To ensure correct operation for most cases:
If h < H (2.3 m), minimum S = 3 m
If h > H or S < 3 m, contact your Carrier distributor to evaluate the various possible arrangements.
H
S
h
Anti-vibration
mounts
3.11 - Underneath a roof.
The upper part of the machine (on top of the fans) must not be covered.
If the floor space requires the machine to be partially covered, contact your Carrier distributor to assess the various installation option.
3 - DIMENSIONS, CLEARANCES