T-305
47
1. Depress the ALT MODE key and scroll to Code
dC30.
2. Depress and hold the ENTER key for five seconds.
3. The DataCORDER will start recording and enter the
date in the trip start data.
4.7.3 Complete Inspection
Allow unit to run for 5 minutes to stabilize conditions and
perform a pre--trip diagnosis in accordance with the
following paragraph.
4.8 PRE-TRIP DIAGNOSIS
CAUTION
Pre-trip inspection should not be per-
formed with critical temperature cargoes in
the container.
CAUTION
When Pre-Trip key is pressed, dehumidifi-
cation and bulb mode will be deactivated.
At the completion of Pre-Trip activity, dehu-
midification and bulb mode must be reacti-
vated.
Pre-Trip diagnosis provides automatic testing of the unit
components using internal measurements and
comparison logic. The program will provide a “PASS” or
“FAIL” display to indicate test results.
The testing begins with access to a pre-trip selection
menu. The user may have the option of selecting one of
three automatic tests (depending on software revision
installed). These tests will automatically perform a
series of individual pre--trip tests. The user may also
scroll down to select any of the individual tests. The
contents of the menus are as follows:
PRE-TRIP SELECTION MENU
Auto or Auto 1 Auto 2*
Auto 3
P1, P2, P3, P4,
P5, P6, rSLts
P, P, P1, P2,
P3, P4,P, P5,
P6, P7, P8, P9,
P10, rSLts
P1, P2, P3, P4,
P5, P6, P7, P8,
rSLts
A detailed description of the pre-trip test codes is listed
in Table 8, page 38. If no selection is made, the pre-trip
menu selection process will terminate automatically.
However, dehumidification and bulb mode must be
reactivated manually if required.
Scrolling down to the “rSLts” code and pressing ENTER
will allow the user to scroll through the results of the last
pre--trip testing run. If no pre--testing has been run (or an
individual test has not been run) since the unit was
powered up “--------” will be displayed.
To start a pre--trip test, do the following:
NOTE
1. Prior to starting tests, verify that unit
voltage (Function Code Cd 07) is within
tolerance and unit amperage draw
(Function Codes Cd04, Cd05, Cd06) is
within expected limits. Otherwise, tests
may fail incorrectly.
2. All alarms must be rectified and cleared
before starting tests.
3.
Pre-trip may also be initiated via
communications. The operation is the
same as for the key pad initiation described
below except that should a test fail, the
pre-trip mode will automatically terminate.
When initiated via communications, a test
may not be interrupted with an arrow key,
but the pre-trip mode can be terminated
with the PRE-TRIP key.
a. Press the PRE-TRIP key. This accesses a test selec-
tion menu.
b. TO RUN AN AUTOMATIC TEST: Scroll through the
selections by pressing the UP ARROW or DOWN
ARROW keys to display AUTO, AUTO 2 or AUTO 3
as desired and then press the AUTO key.
1. The unit will execute the series of tests without any
need for direct user interface. These tests vary in
length, depending on the component under test.
2. While tests are running, “P#-#” will appear on the left
display, where the #’s indicate the test number and
sub-test. The right display will show a countdowntime
in minutes and seconds, indicating how much time
there is left remaining in the test.
CAUTION
When a failure occurs during automatic
testing the unit will suspend operation
awaiting operator intervention.
When an automatic test fails, it will be repeated once .
A repeated test failure will cause “FAIL” to be shown
on the right display, with the corresponding test num-
ber to the left. The user may then press the DOWN
ARROW to repeat the test, the UP ARROW to skip to
the next test or the PRE--TRIP key to terminate test-
ing. The unit will wait indefinitely, until the user manu-
ally enters a command.
CAUTION
When Pre--Trip test Auto 2 runs to comple-
tion without being interrupted, the unit will
terminate pre-trip and display “Auto 2”
“end.” The unit will suspend operation until
the user depresses the ENTER key, or a 2
hour time interval has elapsed.
When an Auto test runs to completion without a failu-
re, the unit will exit the pre-trip mode, and return to
normal control operation. If configuration variable
CnF41 is set to IN, a datacorder trip start will be en-
tered. If CnF41 is set to OUT, the trip start will not be
entered. However, dehumidification and bulb mode
must be reactivated manually if required.
Содержание 69NT40-489-100 Series
Страница 2: ......
Страница 4: ......
Страница 14: ...Safety 10 T 305...
Страница 28: ...4 T 305...
Страница 40: ...16 T 305...
Страница 50: ...26 T 305 Figure 12 Standard Configuration Report...
Страница 112: ...88 T 305...
Страница 163: ...139 T 305 CFS KA6 CFA1 QC1 FDH HST RRS SINGLE SENSOR ONLY Figure 88 Wiring Diagram Sheet 2 of 2...
Страница 164: ...140 T 305...
Страница 167: ...143 T 305 Based on drawings 62 10526 Rev and 62 10736 Rev Figure 90 Electrical Schematic CA...
Страница 168: ...144 T 305 ALTERNATE CONFIGURATION Figure 91 Electrical Wiring Diagram Controlled Atmosphere Sheet 1 of 2...
Страница 169: ...145 T 305 F Figure 88 E Figure 88 Figure 91 Electrical Wiring Diagram Controlled Atmosphere Sheet 2 of 2...
Страница 172: ...148 T 305 Figure 93 Electrical Wiring Diagram Sheet 1 of 2 Units not modified to include the N2 Purity Solenoid Valve...
Страница 174: ...150 T 305...