82
T-305
1. The capacitors are located on the unit sidewall
above the evaporator fan deck, and may be
removed by two methods:
(a.)
If container is empty
, open upper rear panel of
the unit. The capacitors will be on the right and
may be serviced after disconnecting power
plug.
(b.)
If container is full,
turn the unit power OFF and
disconnect power plug. Remove the upper
fresh air makeup vent.
WARNING
With power OFF discharge the capacitor
and disconnect the circuit wiring.
c. Checking the capacitor
If the capacitor is suspected of malfunction, you may
choose to simply replace it. Direct replacement requires
a capacitor of the same value. Two methods for
checking capacitor function are:
1.
Volt-ohmmeter set on RX 10,000 ohms.
Connect ohmmeter leads across the capacitor
terminals and observe the meter needle. If the capacitor
is good, the needle will make a rapid swing toward zero
resistance and then gradually swing back toward a very
high resistance reading. The reading should read about
330,000 ohms (for a good capacitor) due to the
discharge resistors.
If the capacitor has failed open, the ohmmeter needle
will not move when the meter probes touch the
terminals. If the capacitor is shorted, the needle will
swing to zero resistance position and stay there.
2.
Capacitor analyzer:
The function of the analyzer is to read the microfarad
value of a capacitor and to detect insulation breakdown
under load conditions. The important advantages of a
analyzer are its ability to locate capacitors that have
failed to hold their microfarad ratings, or those that are
breaking down internally during operation. It is also
useful in identifying capacitors when their microfarad
rating marks have become unreadable
.
Table 17. Wear Limits For Compressors
PART NAME
FACTORY MAXIMUM
FACTORY MINIMUM
MAXIMUM WEAR
BEFORE REPAIR
inches
mm
inches
mm
inches
mm
MAIN BEARING
Main Bearing Diameter
1.6268
41.3207
.0020
0.0508
Main Bearing Journal Diameter
1.6233
41.2318
.0020
0.0508
PUMP END
Main Bearing Diameter
1.3760
34.9504
.0020
0.0508
Main Bearing Journal Diameter
1.3735
34.8869
.0020
0.0508
CONNECTING ROD
1.3768
34.9707
.0020
0.0508
Piston Pin Bearing
0.6878
17.4701
.0010
0.0254
CRANKPIN DIAMETER
1.3735
34.8869
.0025
0.0635
Throw
1.072
27.2288
1.070
27.1780
THRUST WASHER (Thickness)
0.154
3.9116
0.1520
03.8608
.0250
0.6350
CYLINDERS
Bore
2.0010
50.8254
.0020
0.0508
Piston (Diameter)
1.9860
50.4444
.0020
0.0508
Piston Pin (Diameter)
0.6873
17.4574
.0010
0.0254
Piston Ring Gap
0.013
00.3302
0.0050
00.1270
.0250
0.6350
Piston Ring Side Clearance
0.002
00.0508
0.0010
00.0254
.0020
0.0508
Содержание 69NT40-489-100 Series
Страница 2: ......
Страница 4: ......
Страница 14: ...Safety 10 T 305...
Страница 28: ...4 T 305...
Страница 40: ...16 T 305...
Страница 50: ...26 T 305 Figure 12 Standard Configuration Report...
Страница 112: ...88 T 305...
Страница 163: ...139 T 305 CFS KA6 CFA1 QC1 FDH HST RRS SINGLE SENSOR ONLY Figure 88 Wiring Diagram Sheet 2 of 2...
Страница 164: ...140 T 305...
Страница 167: ...143 T 305 Based on drawings 62 10526 Rev and 62 10736 Rev Figure 90 Electrical Schematic CA...
Страница 168: ...144 T 305 ALTERNATE CONFIGURATION Figure 91 Electrical Wiring Diagram Controlled Atmosphere Sheet 1 of 2...
Страница 169: ...145 T 305 F Figure 88 E Figure 88 Figure 91 Electrical Wiring Diagram Controlled Atmosphere Sheet 2 of 2...
Страница 172: ...148 T 305 Figure 93 Electrical Wiring Diagram Sheet 1 of 2 Units not modified to include the N2 Purity Solenoid Valve...
Страница 174: ...150 T 305...