110
T-305
Table 25. Controlled Atmosphere Pre-Trip Test Codes -- Continued
CODE
NO.
TITLE
DESCRIPTION
P4-0
Carbon Dioxide
Zero Calibration
This test will attempt a zero-point calibration of the carbon dioxide sensor using
the nitrogen stream, and will run for up to 10 minutes and 30 seconds.
Pass/Fail Criteria:
Passes for a successful calibration. Fails otherwise.
P4-1
Oxygen Sensor
Zero Calibration
This test will attempt a zero-point calibration of the oxygen sensor using a
calibration gas, and will run for up to 12 minutes.
Pass/Fail Criteria:
Passes for a successful calibration. Fails otherwise.
NOTE
If test P4-1 fails, then recheck after test P6-0.
P4-2
Carbon Dioxide
Sensor Check
This test will check the span of the carbon dioxide sensor using a calibration
gas, and will run for up to eight minutes.
Pass/Fail Criteria:
Passes for a successful check. Fails otherwise.
P5-0
System
Performance Tests
Requirements:
Valid oxygen sensor calibration values must be available.
(Zero-point and span.) The membrane temperature should be within 3
_
C of
setpoint. However, this test will not fail if this requirement is not met.
Setup:
This test will check the nitrogen percentage from the membrane, and
will run for up to 10 minutes.
Pass/Fail Criteria:
Passes for a successful check with a nitrogen range greater
than 97.5%. Fails otherwise.
P5-1
System
Performance Tests
Requirements:
Valid oxygen sensor calibration values must be available.
(Zero-point and span.) The membrane temperature should be within 3
_
C of
setpoint. However, this test will not fail if this requirement is not met.
Setup:
This test will check the nitrogen percentage from the membrane while
the nitrogen purity valve is energized, and will run for up to 10 minutes.
Pass/Fail Criteria:
Passes, with P5-1 displayed, for a successful check as
defined by the following: N2 range between 88 and 97%. Fails otherwise.
P6-0
Carbon Dioxide
Zero Calibration
This test will attempt a zero-point calibration of the carbon dioxide sensor using
the nitrogen stream, and will run for up to 10 minutes and 30 seconds.
Pass/Fail Criteria:
Passes for a successful calibration. Fails otherwise.
P6-0 is the same as, but independent from P4-0, and is not run during the Auto
Mode of Pre-Trip.
Содержание 69NT40-489-100 Series
Страница 2: ......
Страница 4: ......
Страница 14: ...Safety 10 T 305...
Страница 28: ...4 T 305...
Страница 40: ...16 T 305...
Страница 50: ...26 T 305 Figure 12 Standard Configuration Report...
Страница 112: ...88 T 305...
Страница 163: ...139 T 305 CFS KA6 CFA1 QC1 FDH HST RRS SINGLE SENSOR ONLY Figure 88 Wiring Diagram Sheet 2 of 2...
Страница 164: ...140 T 305...
Страница 167: ...143 T 305 Based on drawings 62 10526 Rev and 62 10736 Rev Figure 90 Electrical Schematic CA...
Страница 168: ...144 T 305 ALTERNATE CONFIGURATION Figure 91 Electrical Wiring Diagram Controlled Atmosphere Sheet 1 of 2...
Страница 169: ...145 T 305 F Figure 88 E Figure 88 Figure 91 Electrical Wiring Diagram Controlled Atmosphere Sheet 2 of 2...
Страница 172: ...148 T 305 Figure 93 Electrical Wiring Diagram Sheet 1 of 2 Units not modified to include the N2 Purity Solenoid Valve...
Страница 174: ...150 T 305...