114
T-305
Venting the container when a power failure occurs
(this procedure should only be used in emer-
gency situations)
In case of a power failure to the unit, there is no
emergency provision to unlock the automatic door
interlock system:
DANGER
WHEN OVERRIDING THE CA CONTROLLER,
THE OPERATOR MUST BE AWARE OF THE
IMMEDIATE DANGER OF UNCONSCIOUS-
NESS AND DEATH. THE OPERATOR MUST
READ AND UNDERSTAND ALL WARNING
LABELS AND SAFETY INSTRUCTIONS BE-
FORE PROCEEDING WITH THE EMERGEN-
CY BYPASS PROCEDURE.
To enter the container in a true emergency situation, do
the following:
1 Ensure at least two persons are present. Oneperson
is to act in a supervisory manner, and that person is
charged with the responsibility to ensure all proce-
dures are performed correctly and all waiting times
have expired before allowing entry.
2 Open the fresh air makeup vent 100% (fully open).
Avoid any direct breathing of venting gases from the
air makeup vent.
3 To enter the container, the interlock system must be
removed. To remove the system, remove the center
bolt from the catch or remove the four screws holding
the interlock system to the container door.
WARNING
Low oxygen levels inside container. Venti-
late container before entering. Stay away
from doors while venting.
4 Fully open container doors.
5 Pull back the curtain (poly sheet) to accelerate the
time of a complete ambient air exchange.
6 Step away from the container rear doors. Do not
close doors. Wait 30 minutes prior to entry or unload-
ing of the container. Wait 45 minutes before climbing
on contents inside of the container.
7 If access to the container is necessary (i.e., life and
death situations) prior to the safety venting proce-
dures being performed, then: only rescue personnel
trained in safety procedures in removing victims
from hazardous atmospheres are to be allowed
entry into the container at this point.
8 All other personnel are to stay well clear of the doors.
CONTAINER REAR DOOR VIEW
REMOVE OR CUT
AS REQUIRED
Figure 66 Emergency Bypass for the Door Interlock System
Содержание 69NT40-489-100 Series
Страница 2: ......
Страница 4: ......
Страница 14: ...Safety 10 T 305...
Страница 28: ...4 T 305...
Страница 40: ...16 T 305...
Страница 50: ...26 T 305 Figure 12 Standard Configuration Report...
Страница 112: ...88 T 305...
Страница 163: ...139 T 305 CFS KA6 CFA1 QC1 FDH HST RRS SINGLE SENSOR ONLY Figure 88 Wiring Diagram Sheet 2 of 2...
Страница 164: ...140 T 305...
Страница 167: ...143 T 305 Based on drawings 62 10526 Rev and 62 10736 Rev Figure 90 Electrical Schematic CA...
Страница 168: ...144 T 305 ALTERNATE CONFIGURATION Figure 91 Electrical Wiring Diagram Controlled Atmosphere Sheet 1 of 2...
Страница 169: ...145 T 305 F Figure 88 E Figure 88 Figure 91 Electrical Wiring Diagram Controlled Atmosphere Sheet 2 of 2...
Страница 172: ...148 T 305 Figure 93 Electrical Wiring Diagram Sheet 1 of 2 Units not modified to include the N2 Purity Solenoid Valve...
Страница 174: ...150 T 305...