Ductable air-cooled scroll
chillers and heat pumps
8
5. T
ECHNICAL
CHARACTERISTICS
HEE version
30PA/PH
90HEE
100HEE
120HEE
160HEE
180HEE
Cooling
capacities
Net cooling capacity
(kW)
18,40
21,00
25,50
31,40
35,70
Net power input
(kW)
7,20
7,95
9,10
11,50
13,60
Net ef
fi
ciency
EER
2,55
2,64
2,81
2,74
2,62
Seasonal ef
fi
ciency
ESEER
2,89
2,99
3,20
3,14
3,03
Heating
capacities
Net heating capacity
(kW)
21,40
23,90
29,30
36,40
42,50
Net power input
(kW)
7,10
7,90
9,50
11,90
13,90
Net ef
fi
ciency
COP
3,03
3,03
3,08
3,05
3,05
Seasonal ef
fi
ciency
Average climate
SCOP
2,98
2,95
3,29
3,18
3,09
ŋs Heat
116%
115%
129%
124%
121%
Prated (kW)
15,92
17,74
21,94
26,77
30,87
Seasonal ef
fi
ciency
Warmer climate
SCOP
3,41
3,58
3,82
3,67
3,65
ŋs Heat
134%
140%
150%
144%
143%
Prated (kW)
13,09
14,68
18,01
22,41
25,89
Outdoor
circuit
plug-fan
Nominal air
fl
ow (m
3
/h)
6500
7000
10000
12200
14000
Nominal available static pressure (mm.w.c.)
20
Maximum available static pressure (mm.w.c.)
63,7
70,3
45,6
65,1
62,7
Number / diameter
1 / 500
1 / 560
2 / 560
Motor output (kW)
2,7
2,8
3,0
2 x 3,0
Power input (kW)
1,33
1,21
1,87
2,20
2,52
Speed (r.p.m.)
1700
1780
1500
1500
Indoor
circuit
Nominal water
fl
ow (m
3
/h)
3,2
3,7
4,5
5,4
6,2
Pressure drop (m.w.c.)
1,6
2,1
1,6
2,4
3,1
Minimum water
fl
ow (m
3
/h)
2,5
2,9
3,4
4,1
4,6
Maximum water
fl
ow (m
3
/h)
6,6
7,4
9,1
11,3
12,8
Type of hydraulic connections
Rosca gas
Diameter of connections
1 1/4” M
1 1/2” M
Compressor
Type
Scroll
Number of compressors / stages / circuits
1
Oil type
Copeland 3MAF 32 cST, Danfoss POE 160 SZ, ICI Emkarate RL 32 CF, Mobil EAL Artic 22 CC
Volume of oil (l)
3,0
3,3
3,3
3,3
6,2
Refrigerant
Type
R-410A
Global warming potential (GWP)
2.088
Charge (kg)
6,0
6,3
6,8
8,9
9,2
Environment impact (tCO
2
e)
12,5
13,2
14,2
18,6
19,2
Electrical
characteristics
Electrical power supply
400 V / III ph / 50 Hz (±10%)
Power supply
3 Hilos + Neutro
Maximum
absorbed
current
Compressor (A)
15,2
17,3
20,5
25,4
30,5
Fan (A)
4,2
4,3
4,6
9,2
9,2
Control (A)
0,9
0,9
0,9
0,9
0,9
Total (A)
20,3
22,5
26,0
35,5
40,6
Dimensions
Length (mm)
1117
1398
2113
Width (mm)
860
860
860
Height (mm)
1447
1727
1447
Weight
Empty (kg)
294
351
368
450
455
In operation (kg)
298
358
376
465
468
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for outlet water temperature conditions of 7ºC and 35ºC outdoor temperature.
Heating capacity calculated in accordance with the EN-14511-2013 standard given for outlet water temperature conditions of 45ºC and 6ºC WB outdoor temperature.
Total power input by compressor, motorised fan and electronic control under nominal conditions, calculated in accordance with the EN-14511-2013 standard. Options are not
included.
European Seasonal Energy Ef
fi
ciency Ratio (ESEER) obtained in accordance with the calculation conditions established by the certi
fi
cation body EUROVENT.
Values calculated in accordance with the EN-14825-2013 standard given for bivalente temperature of -5ºC in average climate and 2ºC in warmer climate.
Motors that are more energy ef
fi
cient than what is established by the ErP 2015 standard.
Climatic warming potential of a kilogram of
fl
uorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years.
Содержание 30PA
Страница 2: ......
Страница 4: ......
Страница 34: ...Ductable air cooled scroll chillers and heat pumps 34 Notes...
Страница 35: ......