Location designation

Before moving the unit, it must be checked that all panels are fastened 
in place. Lift and lower with care.
When choosing the location, whatever may be the selected fashion, the 
following precautions have to be taken into consideration:
-  It is mandatory to comply with norm EN 378-3 on Safety and 

Environmental Requirements. Part 3: "In situ" installation and 
protection to people.

-   The area where the unit will be located must be perfectly accessible for 

cleaning and maintenance operations (check minimum free space for 
maintenance). Leave enough space for air circulation around the unit.

-  Check that the unit is perfectly levelled.
-   It is necessary to check that the surface of the 

fl

 oor or the structure 

supports the weight of the unit (please, consult the weight of the unit 
in the section “Anchorage for silent-blocks”). 

-   Foresee appropriate damping devices in all the installation so that 

noise and vibration transmission is avoided (refer to the “Anchorage 
for silent-blocks”). 
In the event of assembling directly on silent-blocks to the ground, 
it is recommended that a template of the unit’s footprint with the 
anchoring points of the silent-blocks be made.

8. L

OCATION

 

AND

 

ASSEMBLING

With the help of the crane or the forklift truck, the unit will be raised 
to a suf

fi

 cient height that the silent-blocks can be screwed into its 

base. The 4 silent-blocks must remain oblique and the interiors 
perpendicular to the unit. 
M10 metric threads have been provided for their placement in the 
supports indicated in the following section “Anchorage for silent-
blocks”. A hex key 17 or Allen 
wrench 8 will be used for this 
operation based on the type 
of screw used.
This image shows how the 
silent-block option that can 
be supplied for this unit is 

fi

 xed to the unit.

Since it is an unit designed to work indoors, some speci

fi

 c installation 

norms must be followed:
-  Ensure that the location of the supply and return grilles does not 

generate air recirculation.

-  Check that there are no obstructions in the air supply and return grille 

slats due to being tightly closed.

Minimum free space for commissioning and maintenance operations

1m

1m

0,5m

A

30PA/PH/PAC/PHC

A (m)

90STD a 100STD

1,2

120STD a 180STD

1,5

30PA/PH/PAC/PHC

A (m)

90HEE

1,2

100HEE a 120HEE

1,5

160HEE a 180HEE

1,2

Содержание 30PA

Страница 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS 30PA PH PAC PHC Nominal cooling capacity 17 7 36 0 kW Nominal heating capacity 21 8 42 6 kW 50 Hz Ductable air cooled scroll chillers and heat pumps Original...

Страница 2: ......

Страница 3: ...rage for silent blocks 12 Sound level 12 9 Checking before commissioning 13 Electrical connections 13 Checks in the centrifugal fan STD version 14 Checks on the plug fan HEE version 14 Air ducts conne...

Страница 4: ......

Страница 5: ...two versions STD Standard HEE High Energy Efficiency These units have been made for operation indoors in the production of hot and or cold water applicable to heating cooling and industry They are equ...

Страница 6: ...in case of a leak to atmospheric pressure the liquid phase evaporates The resulting vapours are heavier than air and can displace the technician local air In case of an accidental discharge in a clos...

Страница 7: ...kW 7 31 8 90 9 90 12 90 14 20 Net efficiency COP 2 97 2 94 3 00 2 97 3 01 Seasonal efficiency Average climate SCOP 3 11 3 12 3 07 2 95 2 95 s Heat 121 122 120 115 115 Prated kW 16 77 19 19 21 82 26 3...

Страница 8: ...foss POE 160 SZ ICI Emkarate RL 32 CF Mobil EAL Artic 22 CC Volume of oil l 3 0 3 3 3 3 3 3 6 2 Refrigerant Type R 410A Global warming potential GWP 2 088 Charge kg 6 0 6 3 6 8 8 9 9 2 Environment imp...

Страница 9: ...tained in accordance with the calculation conditions established by the certification body EUROVENT Values calculated in accordance with the EN 14825 2013 standard given for bivalente temperature of 5...

Страница 10: ...ation of the load for transport and in particular the maximum speed Transport The unit must be handled with care to avoid transport damage Thus we recommend Do not dispose of the transport supports or...

Страница 11: ...mbling directly on silent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made 8 LOCATION AND ASSEMBLING With the help...

Страница 12: ...unit and flexible connections in the hydraulic tubes If necessary an acoustic technician must commission a study Sound pressure level Measurement conditions in a clear field measured at a distance of...

Страница 13: ...electrical connections before energizing the unit Check that the automatic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V...

Страница 14: ...ning the tensor screw The belt tension must be checked after 24 hours of motor operation Attention Before performing these operations it is necessary to verify that the unit is disconnected from mains...

Страница 15: ...se and vibration transmission Flexible connections Optionally these units can be sent with flexible connections for supply and return air In case of asking together for flexible connections and damper...

Страница 16: ...a stable temperature during the defrosting cycles Hydraulic connections 30PA PH PAC PHC Minimum volume I Minimum flow m3 h Maximum flow m3 h 90STD 101 2 2 6 2 100STD 120 2 7 7 4 120STD 143 3 1 8 8 16...

Страница 17: ...be treated by using materials compatible with these characteristics whether stainless steel or titanium The units hydraulic circuits are made of copper pipes The exchanger plates are made of AISI 316...

Страница 18: ...t leaks and condensation Ensure that the material used is steam barrier type Otherwise cover the insulation using appropriate protection The water must be analysed and the circuit must be set out acco...

Страница 19: ...clogging of the plate exchanger The following graph represents the pressure drop for that filter 1 2 20 25 3 4 5 6 7 8 9 10 15 2 3 10 15 20 6 7 4 5 8 9 9 0 H E E 1 0 0 H E E 1 2 0 H E E 1 6 0 H E E 1...

Страница 20: ...37 0 55 0 75 0 9 1 5 0 55 Maximum abs current A 1 4 2 0 2 3 2 7 4 0 2 0 Minimum water flow m3 h 1 2 1 2 1 2 3 0 4 8 3 0 Maximum pressure m w c 20 7 28 0 30 3 29 5 31 6 20 6 Maximum water flow m3 h 5 4...

Страница 21: ...s stipulation is the only one allowing a best operation of the motorized damper with a homogeneous flow of the air In order to remove the damper it is necessary to unscrew from the unit and disconnect...

Страница 22: ...valves The circulation pump can only work in a closed circuit The command is performed from a thermostat located on the unit Attention a detailed attention must carried with the selection of the expa...

Страница 23: ...available pressure m w c Flow m3 h 6 7 5 3 4 Pump 9 0 S T D t o 1 0 0 S T D 9 0 H E E t o 1 0 0 H E E 1 2 0 S T D t o 1 8 0 S T D 1 2 0 H E E t o 1 8 0 H E E 3 4 1 2 5 6 Hydraulic connections of the...

Страница 24: ...r circulation control A differential pressure switch detains the operation of the unit when it does not detect water circulation Defrost control This control s mission is to eliminate the ice that mig...

Страница 25: ...ll type compressors and have a phase control relay Verify that they turn in the correct direction and if not reverse the power wires COMPRESOR SCROLL COMPROBAR SENTIDO DE GIRO COMPRESSEUR SCROLL V RIF...

Страница 26: ...this means that the mesh filter is obstructed it must be disassembled and cleaned Repeat until the obstruction is eliminated from the filter Once the circuit is free of contaminating elements read the...

Страница 27: ...given in this brochure must be respected and complied with to guarantee a correct operation of the units Next several possible operation problems are stated which could happen if the conditions of the...

Страница 28: ...dirt measuring the difference in temperature at the piping level at the inlet and at the outlet of the dehydrant If necessary replace Mesh filter It is also necessary to install a filter in the hydra...

Страница 29: ...pressure regulation damper in the STD version it is advisable to check the state of the servomotor Filter in the return air optional Clean usually Depending on the installation conditions the filter a...

Страница 30: ...intoxication fire and explosion linked to the refrigerant At the end of its useful life the refrigerant must be retrieved and recycled as per the current regulations Oil Oils used for cooling machines...

Страница 31: ...c Replace filter d Search for leaks complete charge e Temperature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise h...

Страница 32: ...OVERVIEW OF THE INSTALLATION Air cooled chillers air water heat pumps Installation sketch and units location Telephone Installer Responsible for installation and or commissioning Installation work ref...

Страница 33: ...ulation pump Secundary emission system Emission control system Two ways Three ways Manometers reading m w c Pump Suction __________Discharge ________ Diff _______ Unit Inlet_____________Outlet________...

Страница 34: ...Ductable air cooled scroll chillers and heat pumps 34 Notes...

Страница 35: ......

Страница 36: ...Order No 10057 06 2016 Supersedes order No 08 2015 Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Отзывы: