Carrier 30PA Скачать руководство пользователя страница 12

Ductable air-cooled scroll 

chillers and heat pumps

12

Anchorage for silent-blocks

Note:

 all the anchorings are bolt and nut type.

30PAC/

PHC 

Distances (mm)

Reactions in the supports (kg)

A

B

C

Weight in

service

R1

R2

R3

R4

90STD

896

760

65

335

81

97

86

71

100STD

896

760

65

345

82

99

90

73

120STD

1166

760

65

410

99

117

107

87

160STD

1166

760

65

428

102

124

113

90

180STD

1166

760

65

429

104

123

111

91

90HEE

896

760

65

327

77

84

87

79

100HEE

1166

760

65

390

88

109

107

86

120HEE

1166

760

65

408

100

101

104

103

160HEE

1892

760

65

497

109

130

140

118

180HEE

1892

760

65

503

110

132

142

119

30PA/

PH 

Distances (mm)

Reactions in the supports (kg)

A

B

C

Weight in

service

R1

R2

R3

R4

90STD

896

760

65

306

66

101

87

52

100STD

896

760

65

315

69

93

84

60

120STD

1166

760

65

379

89

112

101

77

160STD

1166

760

65

397

92

119

107

79

180STD

1166

760

65

396

93

119

105

79

90HEE

896

760

65

298

64

100

85

50

100HEE

1166

760

65

358

63

127

116

52

120HEE

1166

760

65

376

88

112

100

77

160HEE

1892

760

65

465

69

177

163

56

180HEE

1892

760

65

468

71

178

163

56

B

A

C

M10

R1

R2

R3

R4

Sound level

These units have been designed to operate with a low sound level. 
In any case, in the design of the installation, it must be taken into 
consideration: the outdoor environment for the acoustic radiation, the 
type of building for the noise transmitted in the air and the solid elements 
for the vibration transmission. 
To reduce the transmissions through solid matter to the maximum, we 
recommend installing damping devices between the 

fl

 oor or structure 

and the frame of the unit and 

fl

 exible connections in the hydraulic tubes.

If necessary, an acoustic technician must commission a study.

Sound pressure level

Measurement conditions: in a clear 

fi

 eld, measured at a distance of 10 

metres, directivity 2 and at 1,5 metres from the ground.

Note:

 The sound pressure level depends on the installation conditions and, as 

such, is only indicated as a guide. Values obtained according to standard ISO 3744.

Unit sound power level

Measurement conditions: ducted discharge and return. For nominal 
operating conditions EN 14511 – COOLING and HEATING modes.
Acoustic power reference: 10E-12 W, tolerance of ±2 dB (partial charge 
of ±4 dB).

Note:

 The unit has acoustic insulating cover for compressor

 

(Low Noise version).

30PA/PH/

PAC/PHC

STD version

90STD 100STD 120STD 160STD 180STD

63 Hz

dB(lin)

73,8

74,2

74,4

74,4

74,4

125 Hz

dB(lin)

73,2

73,6

73,8

73,8

73,8

250 Hz

dB(lin)

70,2

70,6

70,8

70,8

70,8

500 Hz

dB(lin)

65,3

65,7

65,9

65,9

65,9

1000 Hz

dB(lin)

63,0

63,4

63,6

63,6

63,6

2000 Hz

dB(lin)

62,2

62,6

62,8

62,8

62,8

4000 Hz

dB(lin)

58,2

58,6

58,8

58,8

58,8

8000 Hz

dB(lin)

49,3

49,7

49,9

49,9

49,9

Total

dB(A)

69,4

69,8

70,0

70,0

70,0

30PA/PH/

PAC/PHC

HEE version

90HEE 100HEE 120HEE 160HEE 180HEE

63 Hz

dB(lin)

71,1

73

73,1

73,1

73,1

125 Hz

dB(lin)

70,9

72,8

72,9

72,9

72,9

250 Hz

dB(lin)

67,5

69,4

69,5

69,5

69,5

500 Hz

dB(lin)

65,4

67,3

67,4

67,4

67,4

1000 Hz

dB(lin)

62,4

64,3

64,4

64,4

64,4

2000 Hz

dB(lin)

59,5

61,3

61,5

61,5

61,4

4000 Hz

dB(lin)

56,5

58,4

58,5

58,5

58,5

8000 Hz

dB(lin)

49,4

51,3

51,4

51,4

51,4

Total

dB(A)

68,0

69,9

70,0

70,0

70,0

30PA/PH/

PAC/PHC

STD version

90STD 100STD 120STD 160STD 180STD

Total

dB(A)

38,0

38,4

38,4

38,4

38,4

30PA/PH/

PAC/PHC

HEE version

90HEE 100HEE 120HEE 160HEE 180HEE

Total

dB(A)

36,6

38,3

38,4

38,4

38,4

Содержание 30PA

Страница 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS 30PA PH PAC PHC Nominal cooling capacity 17 7 36 0 kW Nominal heating capacity 21 8 42 6 kW 50 Hz Ductable air cooled scroll chillers and heat pumps Original...

Страница 2: ......

Страница 3: ...rage for silent blocks 12 Sound level 12 9 Checking before commissioning 13 Electrical connections 13 Checks in the centrifugal fan STD version 14 Checks on the plug fan HEE version 14 Air ducts conne...

Страница 4: ......

Страница 5: ...two versions STD Standard HEE High Energy Efficiency These units have been made for operation indoors in the production of hot and or cold water applicable to heating cooling and industry They are equ...

Страница 6: ...in case of a leak to atmospheric pressure the liquid phase evaporates The resulting vapours are heavier than air and can displace the technician local air In case of an accidental discharge in a clos...

Страница 7: ...kW 7 31 8 90 9 90 12 90 14 20 Net efficiency COP 2 97 2 94 3 00 2 97 3 01 Seasonal efficiency Average climate SCOP 3 11 3 12 3 07 2 95 2 95 s Heat 121 122 120 115 115 Prated kW 16 77 19 19 21 82 26 3...

Страница 8: ...foss POE 160 SZ ICI Emkarate RL 32 CF Mobil EAL Artic 22 CC Volume of oil l 3 0 3 3 3 3 3 3 6 2 Refrigerant Type R 410A Global warming potential GWP 2 088 Charge kg 6 0 6 3 6 8 8 9 9 2 Environment imp...

Страница 9: ...tained in accordance with the calculation conditions established by the certification body EUROVENT Values calculated in accordance with the EN 14825 2013 standard given for bivalente temperature of 5...

Страница 10: ...ation of the load for transport and in particular the maximum speed Transport The unit must be handled with care to avoid transport damage Thus we recommend Do not dispose of the transport supports or...

Страница 11: ...mbling directly on silent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made 8 LOCATION AND ASSEMBLING With the help...

Страница 12: ...unit and flexible connections in the hydraulic tubes If necessary an acoustic technician must commission a study Sound pressure level Measurement conditions in a clear field measured at a distance of...

Страница 13: ...electrical connections before energizing the unit Check that the automatic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V...

Страница 14: ...ning the tensor screw The belt tension must be checked after 24 hours of motor operation Attention Before performing these operations it is necessary to verify that the unit is disconnected from mains...

Страница 15: ...se and vibration transmission Flexible connections Optionally these units can be sent with flexible connections for supply and return air In case of asking together for flexible connections and damper...

Страница 16: ...a stable temperature during the defrosting cycles Hydraulic connections 30PA PH PAC PHC Minimum volume I Minimum flow m3 h Maximum flow m3 h 90STD 101 2 2 6 2 100STD 120 2 7 7 4 120STD 143 3 1 8 8 16...

Страница 17: ...be treated by using materials compatible with these characteristics whether stainless steel or titanium The units hydraulic circuits are made of copper pipes The exchanger plates are made of AISI 316...

Страница 18: ...t leaks and condensation Ensure that the material used is steam barrier type Otherwise cover the insulation using appropriate protection The water must be analysed and the circuit must be set out acco...

Страница 19: ...clogging of the plate exchanger The following graph represents the pressure drop for that filter 1 2 20 25 3 4 5 6 7 8 9 10 15 2 3 10 15 20 6 7 4 5 8 9 9 0 H E E 1 0 0 H E E 1 2 0 H E E 1 6 0 H E E 1...

Страница 20: ...37 0 55 0 75 0 9 1 5 0 55 Maximum abs current A 1 4 2 0 2 3 2 7 4 0 2 0 Minimum water flow m3 h 1 2 1 2 1 2 3 0 4 8 3 0 Maximum pressure m w c 20 7 28 0 30 3 29 5 31 6 20 6 Maximum water flow m3 h 5 4...

Страница 21: ...s stipulation is the only one allowing a best operation of the motorized damper with a homogeneous flow of the air In order to remove the damper it is necessary to unscrew from the unit and disconnect...

Страница 22: ...valves The circulation pump can only work in a closed circuit The command is performed from a thermostat located on the unit Attention a detailed attention must carried with the selection of the expa...

Страница 23: ...available pressure m w c Flow m3 h 6 7 5 3 4 Pump 9 0 S T D t o 1 0 0 S T D 9 0 H E E t o 1 0 0 H E E 1 2 0 S T D t o 1 8 0 S T D 1 2 0 H E E t o 1 8 0 H E E 3 4 1 2 5 6 Hydraulic connections of the...

Страница 24: ...r circulation control A differential pressure switch detains the operation of the unit when it does not detect water circulation Defrost control This control s mission is to eliminate the ice that mig...

Страница 25: ...ll type compressors and have a phase control relay Verify that they turn in the correct direction and if not reverse the power wires COMPRESOR SCROLL COMPROBAR SENTIDO DE GIRO COMPRESSEUR SCROLL V RIF...

Страница 26: ...this means that the mesh filter is obstructed it must be disassembled and cleaned Repeat until the obstruction is eliminated from the filter Once the circuit is free of contaminating elements read the...

Страница 27: ...given in this brochure must be respected and complied with to guarantee a correct operation of the units Next several possible operation problems are stated which could happen if the conditions of the...

Страница 28: ...dirt measuring the difference in temperature at the piping level at the inlet and at the outlet of the dehydrant If necessary replace Mesh filter It is also necessary to install a filter in the hydra...

Страница 29: ...pressure regulation damper in the STD version it is advisable to check the state of the servomotor Filter in the return air optional Clean usually Depending on the installation conditions the filter a...

Страница 30: ...intoxication fire and explosion linked to the refrigerant At the end of its useful life the refrigerant must be retrieved and recycled as per the current regulations Oil Oils used for cooling machines...

Страница 31: ...c Replace filter d Search for leaks complete charge e Temperature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise h...

Страница 32: ...OVERVIEW OF THE INSTALLATION Air cooled chillers air water heat pumps Installation sketch and units location Telephone Installer Responsible for installation and or commissioning Installation work ref...