Ductable air-cooled scroll
chillers and heat pumps
12
Anchorage for silent-blocks
Note:
all the anchorings are bolt and nut type.
30PAC/
PHC
Distances (mm)
Reactions in the supports (kg)
A
B
C
Weight in
service
R1
R2
R3
R4
90STD
896
760
65
335
81
97
86
71
100STD
896
760
65
345
82
99
90
73
120STD
1166
760
65
410
99
117
107
87
160STD
1166
760
65
428
102
124
113
90
180STD
1166
760
65
429
104
123
111
91
90HEE
896
760
65
327
77
84
87
79
100HEE
1166
760
65
390
88
109
107
86
120HEE
1166
760
65
408
100
101
104
103
160HEE
1892
760
65
497
109
130
140
118
180HEE
1892
760
65
503
110
132
142
119
30PA/
PH
Distances (mm)
Reactions in the supports (kg)
A
B
C
Weight in
service
R1
R2
R3
R4
90STD
896
760
65
306
66
101
87
52
100STD
896
760
65
315
69
93
84
60
120STD
1166
760
65
379
89
112
101
77
160STD
1166
760
65
397
92
119
107
79
180STD
1166
760
65
396
93
119
105
79
90HEE
896
760
65
298
64
100
85
50
100HEE
1166
760
65
358
63
127
116
52
120HEE
1166
760
65
376
88
112
100
77
160HEE
1892
760
65
465
69
177
163
56
180HEE
1892
760
65
468
71
178
163
56
B
A
C
M10
R1
R2
R3
R4
Sound level
These units have been designed to operate with a low sound level.
In any case, in the design of the installation, it must be taken into
consideration: the outdoor environment for the acoustic radiation, the
type of building for the noise transmitted in the air and the solid elements
for the vibration transmission.
To reduce the transmissions through solid matter to the maximum, we
recommend installing damping devices between the
fl
oor or structure
and the frame of the unit and
fl
exible connections in the hydraulic tubes.
If necessary, an acoustic technician must commission a study.
Sound pressure level
Measurement conditions: in a clear
fi
eld, measured at a distance of 10
metres, directivity 2 and at 1,5 metres from the ground.
Note:
The sound pressure level depends on the installation conditions and, as
such, is only indicated as a guide. Values obtained according to standard ISO 3744.
Unit sound power level
Measurement conditions: ducted discharge and return. For nominal
operating conditions EN 14511 – COOLING and HEATING modes.
Acoustic power reference: 10E-12 W, tolerance of ±2 dB (partial charge
of ±4 dB).
Note:
The unit has acoustic insulating cover for compressor
(Low Noise version).
30PA/PH/
PAC/PHC
STD version
90STD 100STD 120STD 160STD 180STD
63 Hz
dB(lin)
73,8
74,2
74,4
74,4
74,4
125 Hz
dB(lin)
73,2
73,6
73,8
73,8
73,8
250 Hz
dB(lin)
70,2
70,6
70,8
70,8
70,8
500 Hz
dB(lin)
65,3
65,7
65,9
65,9
65,9
1000 Hz
dB(lin)
63,0
63,4
63,6
63,6
63,6
2000 Hz
dB(lin)
62,2
62,6
62,8
62,8
62,8
4000 Hz
dB(lin)
58,2
58,6
58,8
58,8
58,8
8000 Hz
dB(lin)
49,3
49,7
49,9
49,9
49,9
Total
dB(A)
69,4
69,8
70,0
70,0
70,0
30PA/PH/
PAC/PHC
HEE version
90HEE 100HEE 120HEE 160HEE 180HEE
63 Hz
dB(lin)
71,1
73
73,1
73,1
73,1
125 Hz
dB(lin)
70,9
72,8
72,9
72,9
72,9
250 Hz
dB(lin)
67,5
69,4
69,5
69,5
69,5
500 Hz
dB(lin)
65,4
67,3
67,4
67,4
67,4
1000 Hz
dB(lin)
62,4
64,3
64,4
64,4
64,4
2000 Hz
dB(lin)
59,5
61,3
61,5
61,5
61,4
4000 Hz
dB(lin)
56,5
58,4
58,5
58,5
58,5
8000 Hz
dB(lin)
49,4
51,3
51,4
51,4
51,4
Total
dB(A)
68,0
69,9
70,0
70,0
70,0
30PA/PH/
PAC/PHC
STD version
90STD 100STD 120STD 160STD 180STD
Total
dB(A)
38,0
38,4
38,4
38,4
38,4
30PA/PH/
PAC/PHC
HEE version
90HEE 100HEE 120HEE 160HEE 180HEE
Total
dB(A)
36,6
38,3
38,4
38,4
38,4