Ductable air-cooled scroll
chillers and heat pumps
22
Cooling recovery circuit (optional)
The system consists in a hot water supplying by an heat recovery
system on the compressor(s) discharge gas, on an auxiliary
desuperheater exchanger.
On an heat pump model, the optional desuperheater can be used
whatever the running mode, COOLING or HEATING.
This optional equipment is only available on request, and factory
mounted.
Operating mode
The heat recovery is possible only if the unit is running, on COOLING
mode or on HEAT PUMP mode.
For the same cooling or heating capacity, the desuperheater system
allows a free heating of hot water with a reduction of the total input
power of the unit.
Principle and precaution of hydraulic connection
In order to allow the unit to start up and to run under good conditions,
the circuit must be as short as possible, and the water
fl
ow of the
desuperheater must start slowly to normal operating condition, with a
water
fl
ow equal to 10% of its standard value, and must be calculated
for a hot water inlet temperature of +50°C.
Thus, it is recommended to have a hydraulic diagram making it possible
to obtain very quickly a hot water at the inlet of the desuperheater (3 ways
valve + cont temperature sensor on the exchanger water inlet).
The controller set point must be adjusted to +50°C minimum.
The recovery circuit must be done in accordance with the standards
in force and plan all of the necessary elements in a closed circuit:
circulation pump (optionally supplied), expansion vessel, safety valve,
mesh
fi
lter,
fi
ller, drainer, bleeders, thermometers, pressure gauges and
cut-off and insulation valves.
The circulation pump can only work in a closed circuit. The command
is performed from a thermostat located on the unit.
Attention: a detailed attention must carried with the selection of the
expansion tank, because the recovery water circuit can reach the
temperature of 120°C in the event of stopping of the circulator or non
hot water consumption.
- Install heating elements on all pipes that could be exposed to freezing
temperatures.
PLATES
EXCHARGER
EXPANSION
VESSEL
ELECTRICAL
HEATER
MESH
FILTER
VA
SHUT-OFF
LVE
DRAINAGE
CIRCUIT
SAFETY
VALVE
NO RETURN
-
VALVE
VA
AIR BLEEDER
LVE
THERMOMETER
MANOMETER
CIRCULATOR
PUMP
FILLED
CIRCUIT
3-WAY
VALVE
FLEXIBLE
CONNECTION
Agua de red
A consumo
Opcional
30PA/PH
Min. 50ºC
Technical characteristics of the recovery circuit
30PA/PH/PAC/PHC
STD version
HEE version
90STD
100STD 120STD 160STD 180STD 90HEE
100HEE
120HEE
160HEE
180HEE
Recovery capacity
(kW)
4,4
5,2
6,2
8,1
8,9
4,5
5,2
6,3
7,7
8,8
Nominal water
fl
ow (m
3
/h)
0,38
0,45
0,53
0,70
0,76
0,39
0,44
0,54
0,67
0,76
Pressure drop (m.w.c.)
0,06
0,09
0,17
0,30
0,36
0,07
0,09
0,18
0,27
0,35
Cooling capacity (kW)
17,8
21,3
25,3
33,0
36,2
18,5
21,1
25,6
31,6
35,8
Power input (kW)
6,8
7,9
8,6
10,8
12,7
6,2
7,1
7,8
10,0
11,9
Hydraulic
connections
Type
Threaded
Threaded
Diameter
1” M
1” M
Pump
(optional)
Type
Humid rotor
Humid rotor
Number
1
1
Motor output (kW)
0,05
0,05
Max. absorbed current (A)
0,4
0,4
Avail. pressure (m.w.c.)
(max. pump speed)
5,54
5,45
5,35
5,15
5,07
5,52
5,46
5,34
5,19
5,07
Additional
weight
Recovery circuit (kg)
5,3
5,3
6,8
6,8
6,8
5,3
5,3
6,8
6,8
6,8
Pump (optional) (kg)
3,2
3,2
Capacity recovered by the desuperheater circuit for nominal conditions and recovery water at 50/60ºC.
The change of speed of the pump is made by a button that changes color according to the selected speed (blue: low; green: medium; yellow: high).