Carrier 30PA Скачать руководство пользователя страница 28

Ductable air-cooled scroll 

chillers and heat pumps

28

 Recommendations

-  Do not lean on the unit. A platform must be used to work on a level.

-  Do not lean on the copper refrigerant tubes.

-  Keep the unit clean. 

-  Keep the space surrounding the unit clean and cleared in order to 

avoid accidents and ensure the proper ventilation of the coil.

-  Perform a visual (remains of water or oil below or around the unit) 

and auditory inspection of the entire installation.

-  In general, a corrosion control must be performed on the metallic 

parts of the unit (frame, bodywork, exchangers, electric panel, etc.). 

-  Check that the insulation foam is not unstuck or torn.

-  All the electric connection states must be checked as well, as well 

as the air tightness of the different circuits.

Next, some recommendations are stated for performing the 
maintenance and cleaning of the unit's components:

13. M

AINTENANCE

The minimal maintenance operations and their periodicity will be made 
according to the national regulations. 
Any intervention on the electric cooling components must be made by 
a quali

fi

 ed and authorized technician. 

Technicians who intervene with the unit must use the necessary safety 
equipment (gloves, goggles, insulating clothing, safety shoes, etc.). 
Furthermore, if working around sources of significant noise, we 
recommend the use of noise-dampening headgear.

V-220004

Caution: Before intervening in the unit, cut off main 
power.

Dehydrating 

fi

 lter

- The 

fi

 lter function is to keep the cooling circuit clean and without 

humidity, neutralising the acids that can be found in the cooling circuit. 

-  Verify dirt measuring the difference in temperature at the piping level, 

at the inlet and at the outlet of the dehydrant. 

-  If necessary, replace.

Mesh 

fi

 lter

It is also necessary to install a 

fi

 lter in the hydraulic power supply 

to the unit in order to prevent clogging of the plate exchanger. 

For 30PAC/PHC units, a kit with a stainless steel mesh 

fi

 lter (500 

microns) is also supplied for installation by the installer. Optionally, 
this 

fi

 lter can be supplied for 30PA/PH units. 

- The 

fi

 ltering mesh must be removed and cleaned in order to clean 

the 

fi

 lter.

Plate exchanger

-  The exchangers are 

fi

 tted with thermal insulation. Check that the 

foam is not unstuck or broken.

-  The water quality and the pressure drop must be veri

fi

 ed at the 

exchanger level. After verifying the mesh 

fi

 lter condition, if necessary, 

the exchanger must be cleaned. To this end, a weak solution of 
phosphoric acid 5% must be circulated using the high pressure 
pump. During optimum cleaning, the cleaning solution 

fl

 ow must, as 

a minimum, be 1,5 times the working 

fl

 ow, preferably in the inverse 

circulation mode. This must be followed by thorough rinsing with water 
to remove any acidic residues. It is advisable to circulate a solution 
1%-2% of sodium hydroxide prior to the last rinsing in order to ensure 
that the acid has been neutralised.

-  Any repair or modi

fi

 cation to the plate exchanger is prohibited. It can 

only be replaced by an original part.

Air coil

-  Check that the coil is free from dust and grease. 
-  Cleaning the accumulated dust on the coil can be performed with 

a vacuum cleaner perpendicular to the 

fi

 ns or with a low-pressure 

water cleaner. Grease can be removed with water with degreaser. 
Do not put stress on the 

fi

 ns as they could deform.

Dehydrating

 lter

Plate

exchanger

Differential

pressure switch

Содержание 30PA

Страница 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS 30PA PH PAC PHC Nominal cooling capacity 17 7 36 0 kW Nominal heating capacity 21 8 42 6 kW 50 Hz Ductable air cooled scroll chillers and heat pumps Original...

Страница 2: ......

Страница 3: ...rage for silent blocks 12 Sound level 12 9 Checking before commissioning 13 Electrical connections 13 Checks in the centrifugal fan STD version 14 Checks on the plug fan HEE version 14 Air ducts conne...

Страница 4: ......

Страница 5: ...two versions STD Standard HEE High Energy Efficiency These units have been made for operation indoors in the production of hot and or cold water applicable to heating cooling and industry They are equ...

Страница 6: ...in case of a leak to atmospheric pressure the liquid phase evaporates The resulting vapours are heavier than air and can displace the technician local air In case of an accidental discharge in a clos...

Страница 7: ...kW 7 31 8 90 9 90 12 90 14 20 Net efficiency COP 2 97 2 94 3 00 2 97 3 01 Seasonal efficiency Average climate SCOP 3 11 3 12 3 07 2 95 2 95 s Heat 121 122 120 115 115 Prated kW 16 77 19 19 21 82 26 3...

Страница 8: ...foss POE 160 SZ ICI Emkarate RL 32 CF Mobil EAL Artic 22 CC Volume of oil l 3 0 3 3 3 3 3 3 6 2 Refrigerant Type R 410A Global warming potential GWP 2 088 Charge kg 6 0 6 3 6 8 8 9 9 2 Environment imp...

Страница 9: ...tained in accordance with the calculation conditions established by the certification body EUROVENT Values calculated in accordance with the EN 14825 2013 standard given for bivalente temperature of 5...

Страница 10: ...ation of the load for transport and in particular the maximum speed Transport The unit must be handled with care to avoid transport damage Thus we recommend Do not dispose of the transport supports or...

Страница 11: ...mbling directly on silent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made 8 LOCATION AND ASSEMBLING With the help...

Страница 12: ...unit and flexible connections in the hydraulic tubes If necessary an acoustic technician must commission a study Sound pressure level Measurement conditions in a clear field measured at a distance of...

Страница 13: ...electrical connections before energizing the unit Check that the automatic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V...

Страница 14: ...ning the tensor screw The belt tension must be checked after 24 hours of motor operation Attention Before performing these operations it is necessary to verify that the unit is disconnected from mains...

Страница 15: ...se and vibration transmission Flexible connections Optionally these units can be sent with flexible connections for supply and return air In case of asking together for flexible connections and damper...

Страница 16: ...a stable temperature during the defrosting cycles Hydraulic connections 30PA PH PAC PHC Minimum volume I Minimum flow m3 h Maximum flow m3 h 90STD 101 2 2 6 2 100STD 120 2 7 7 4 120STD 143 3 1 8 8 16...

Страница 17: ...be treated by using materials compatible with these characteristics whether stainless steel or titanium The units hydraulic circuits are made of copper pipes The exchanger plates are made of AISI 316...

Страница 18: ...t leaks and condensation Ensure that the material used is steam barrier type Otherwise cover the insulation using appropriate protection The water must be analysed and the circuit must be set out acco...

Страница 19: ...clogging of the plate exchanger The following graph represents the pressure drop for that filter 1 2 20 25 3 4 5 6 7 8 9 10 15 2 3 10 15 20 6 7 4 5 8 9 9 0 H E E 1 0 0 H E E 1 2 0 H E E 1 6 0 H E E 1...

Страница 20: ...37 0 55 0 75 0 9 1 5 0 55 Maximum abs current A 1 4 2 0 2 3 2 7 4 0 2 0 Minimum water flow m3 h 1 2 1 2 1 2 3 0 4 8 3 0 Maximum pressure m w c 20 7 28 0 30 3 29 5 31 6 20 6 Maximum water flow m3 h 5 4...

Страница 21: ...s stipulation is the only one allowing a best operation of the motorized damper with a homogeneous flow of the air In order to remove the damper it is necessary to unscrew from the unit and disconnect...

Страница 22: ...valves The circulation pump can only work in a closed circuit The command is performed from a thermostat located on the unit Attention a detailed attention must carried with the selection of the expa...

Страница 23: ...available pressure m w c Flow m3 h 6 7 5 3 4 Pump 9 0 S T D t o 1 0 0 S T D 9 0 H E E t o 1 0 0 H E E 1 2 0 S T D t o 1 8 0 S T D 1 2 0 H E E t o 1 8 0 H E E 3 4 1 2 5 6 Hydraulic connections of the...

Страница 24: ...r circulation control A differential pressure switch detains the operation of the unit when it does not detect water circulation Defrost control This control s mission is to eliminate the ice that mig...

Страница 25: ...ll type compressors and have a phase control relay Verify that they turn in the correct direction and if not reverse the power wires COMPRESOR SCROLL COMPROBAR SENTIDO DE GIRO COMPRESSEUR SCROLL V RIF...

Страница 26: ...this means that the mesh filter is obstructed it must be disassembled and cleaned Repeat until the obstruction is eliminated from the filter Once the circuit is free of contaminating elements read the...

Страница 27: ...given in this brochure must be respected and complied with to guarantee a correct operation of the units Next several possible operation problems are stated which could happen if the conditions of the...

Страница 28: ...dirt measuring the difference in temperature at the piping level at the inlet and at the outlet of the dehydrant If necessary replace Mesh filter It is also necessary to install a filter in the hydra...

Страница 29: ...pressure regulation damper in the STD version it is advisable to check the state of the servomotor Filter in the return air optional Clean usually Depending on the installation conditions the filter a...

Страница 30: ...intoxication fire and explosion linked to the refrigerant At the end of its useful life the refrigerant must be retrieved and recycled as per the current regulations Oil Oils used for cooling machines...

Страница 31: ...c Replace filter d Search for leaks complete charge e Temperature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise h...

Страница 32: ...OVERVIEW OF THE INSTALLATION Air cooled chillers air water heat pumps Installation sketch and units location Telephone Installer Responsible for installation and or commissioning Installation work ref...

Страница 33: ...ulation pump Secundary emission system Emission control system Two ways Three ways Manometers reading m w c Pump Suction __________Discharge ________ Diff _______ Unit Inlet_____________Outlet________...

Страница 34: ...Ductable air cooled scroll chillers and heat pumps 34 Notes...

Страница 35: ......

Страница 36: ...Order No 10057 06 2016 Supersedes order No 08 2015 Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Отзывы: