APPENDIX B
—
09FC FREE COOLING MODULE CONTROLLER (CONT)
Service Configuration
Navigation: i-Vu
®
/ Field Assistant: Properties > Control Program
> Configuration > Service Configuration
Point Name – Description
Default/Range
Remote Contact Normal Logic State
– Specifies the remote contact's normal logic state.
D: Open
R: Open/Closed
Fan VFD Run Status Normal Logic State
– Specifies the fan's variable frequency drive run status normal
logic state.
D: Open
R: Open/Closed
Fan VFD Output Type
– Defines the type of fan variable frequency drive output control.
D: 0-10V
R: 0-10V/2-10V
Fan Initial Start Speed
– The speed that the module’s fans are briefly run on initial startup.
D: 100%
R: 0 to 100%
Fan Minimum Speed
– The lowest speed that the module’s fan is commanded when the fans’ variable
frequency drive is enabled.
D: 20%
R: 0 to 100%
Fan Speed PID
– This BACnet Object calculates the amount of fan speed required to satisfy the
Leaving
Water Temp Setpoint
and allows access to the control loop's tuning parameters.
NOTE
: The following default values should be changed only by a technician trained in tuning PI
D Loop algorithms.
R: 0 to 100%
Action
Update Interval
Proportional
Integral
Derivative
Deadband
Bias
direct
1:00 mm:ss
10
5
0
0
0
Bypass Valve Type
– Defines the type of bypass valve analog output control.
D: 0-10V
R: 0-10V/2-10V
Bypass Valve PID
– This BACnet Object calculates the amount of bypass required to satisfy the
Leaving
Water Temp Setpoint
when bypass valve modulation is enabled and allows access to the control loop's
tuning parameters.
NOTE The following default values should be changed only by a technician trained in tuning PI
D Loop algorithms.
R: 0 to 100%
Action
Update Interval
Proportional
Integral
Derivative
Deadband
Bias
reverse
1:00 mm:ss
10
2
0
0
0
System Cool Demand Level
– The system cool demand level being received over the network.
D: 0.00
R: 0 to 3
System Leaving Water Temperature
– Allows using another controller's leaving water temperature sensor
value (system water temperature), to be read over the network. The remote controller must have a network-
accessible leaving water temperature sensor value.
D: -999°F
R: -25 to 125°F
System Entering Water Temperature
– Allows using another controller's entering water temperature
sensor value (system water temperature), to be read over the network. The remote controller must have a
network-accessible entering water temperature sensor value.
D: -999°F
R: -25 to 125°F
System Outdoor Air Temperature
– Allows using another controller's outdoor air temperature value over
the network. The remote controller must have a network accessible outdoor air temperature sensor value.
D: -999°F
R: -50 to 150°F
System Control Setpoint
– Allows using another controller's Control Setpoint value to be read over the
network. The remote controller must have a network-accessible point.
D: -999°F
R: -20 to 65°F
System Occupancy
– Allows reading and using another controller's occupancy status value over the
network. The remote controller must have a network-accessible Occupancy Status point.
D: Unoccupied
R: Unoccupied/Occupied
Equipment Alarm Lamp Initiators
Lvg Water Temp Alarm
– When set to
Enable
, any Leaving Water Temperature Alarm indicated by the
controller also initiates an
Equipment Alarm
and energizes the
Alarm Lamp
binary output.
D: Enable
R: Disable/Enable
Lvg Wtr Sensor Fail Alarm
– When set to Enable, any Leaving Water Temperature Sensor Failure Alarm
indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable
R: Disable/Enable
Ent Water Temp Alarm
– When set to
Enable
, any Entering Water Temperature Alarm indicated by the
controller also initiates an
Equipment Alarm
and energizes the
Alarm Lamp
binary output.
D: Enable
R: Disable/Enable
Ent Wtr Sensor Fail Alarm
– When set to
Enable
, any Entering Water Temperature Sensor Failure Alarm
indicated by the controller also initiates an
Equipment Alarm
and energizes the
Alarm Lamp
binary output.
D: Enable
R: Disable/Enable
Outdoor Air Temp Alarm
– When set to
Enable
, any Outdoor Air Temperature Alarm indicated by the
controller also initiates an
Equipment Alarm
and energizes the
Alarm Lamp
binary output.
D: Enable
R: Disable/Enable
Outdoor Air Sensor Fail Alarm
– When set to
Enable
, an Outdoor Air Temperature Sensor Failure Alarm
indicated by the controller also initiates an
Equipment Alarm
and energizes the
Alarm Lamp
binary output.
D: Enable
R: Disable/Enable
Fan VFD Fail Alarm
– When set to
Enable
, a Fan VFD Failure Alarm indicated by the controller also initiates
an
Equipment Alarm
and energizes the
Alarm Lamp
binary output.
D: Enable
R: Disable/Enable
Lvg Water Temp Hi Alarm
– When set to
Enable
, a High Leaving Water Temperature Alarm indicated by
the controller also initiates an
Equipment Alarm
and energizes the
Alarm Lamp
binary output.
D: Enable
R: Disable/Enable
Negative DeltaT Alarm
– When set to
Enable
, a Negative Differential Temperature Alarm indicated by the
controller also initiates an
Equipment Alarm
and energizes the
Alarm Lamp
binary output.
D: Enable
R: Disable/Enable
Service Test
Service Test
– When set to
Enable
, any output can be overridden for up to 5 minutes. The
Service Test
has
a 1 hour timeout.
D: Disable
R: Disable/Enable
Содержание 09FC020
Страница 8: ...8 Fig 5 09FC 020 Unit Dimensions...
Страница 9: ...9 Fig 6 09FC 030 Unit Dimensions...
Страница 10: ...10 Fig 7 09FC 040 Unit Dimensions...
Страница 11: ...11 Fig 8 09FC 050 Unit Dimensions...
Страница 12: ...12 Fig 9 09FC 060 Unit Dimensions...
Страница 13: ...13 Fig 10 09FC 070 Unit Dimensions...
Страница 14: ...14 Fig 11 09FC 080 Unit Dimensions...
Страница 69: ......