45
nal is applied on the control terminals and/or the bus, the fre
-
quency converter starts.
NOTE: An active HAND-OFF-AUTO signal via digital inputs
has higher priority than the local control keys Hand On –Auto On.
The Reset key resets the frequency converter after an alarm (trip).
See Table 10 for a list of common VFD parameters.
Table 10 —
Common VFD Parameters
Voltage
# of V's
2V
3V
4V
5V
6V
7V
8V
Drive Designation
FVFD-1 FVFD-1 FVFD-1 FVFD-1 FVFD-2 FVFD-1 FVFD-2 FVFD-1 FVFD-2 FVFD-1 FVFD-2
# of Connected Fans
4
6
8
6
4
6
6
7
7
8
8
1-03
Torque
Characteristic
variable
torque
1
1
1
1
1
1
1
1
1
1
1
1-21
Motor Hp
size
dependent
10
15
25.0
20.0
15.0
15
15
20
20
20
20
1-22
Motor Volts
motor
dependent
REFER TO VOLTAGE SPECIFIC TABLE
1-23
Motor
Frequency
Hz
60
60
60
60
60
60
60
60
60
60
60
1-24
Motor
Amperage
size
dependent
REFER TO VOLTAGE SPECIFIC TABLE
1-25
Motor Rpm
size
dependent
1130
1130
1130
1130
1130
1130
1130
1130
1130
1130
1130
1-73
Flying Restart NO
0
0
0
0
0
0
0
0
0
0
0
1-80
Function at
Stop
coast
0
0
0
0
0
0
0
0
0
0
0
1-90
Motor
Thermal
Protection
0
0
0
0
0
0
0
0
0
0
0
0
3-02
Min
Reference
Hz
0
0
0
0
0
0
0
0
0
0
0
3-03
Max
Reference
Hz
60
60
60
60
60
60
60
60
60
60
60
3-13
Type
Reference
remote
1
1
1
1
1
0
0
0
0
0
0
3-15
Src Ref#1
analog input
1
1
1
1
1
1
1
1
1
1
1
3-16
Src Ref#2
no function
0
0
0
0
0
0
0
0
0
0
0
3-41
Ramp Up
s
20
20
20
20
20
20
20
20
20
20
20
3-42
Ramp Down s
20
20
20
20
20
20
20
20
20
20
20
4-10
Motor Speed
Direct
clockwise
0
0
0
0
0
0
0
0
0
0
0
4-12
Motor Speed
Low Limit
Hz
5
5
5
5
5
5
5
5
5
5
5
4-14
Motor Speed
High Limit
Hz
60
60
60
60
60
60
60
60
60
60
60
4-16
Torque Limit size
dependent
150
150
150
150
150
150
150
150
150
150
150
4-18
Current Limit size
dependent
110
110
110
110
110
110
110
110
110
110
110
4-19
Max Output
Frequency
Hz
61
61
61
61
61
61
61
61
61
61
61
5-10
Term#18 Di
Start
8
8
8
8
8
8
8
8
8
8
8
5-12
Di #27
no function
0
0
0
0
0
2
2
2
2
2
2
5-40
Relay 1
running
5
5
5
5
5
5
5
5
5
5
5
6-10
Term#53
Low V
0V
0
0
0
0
0
0
0
0
0
0
0
6-11
Term#53
High V
10V
10
10
10
10
10
10
10
10
10
10
10
8-01
Control Site
digital
0
0
0
0
0
0
0
0
0
0
0
8-02
Control
Source
FC
port=RS485
1
1
1
1
1
1
1
1
1
1
1
8-03
Time Out
Time
s
10
10
10
10
10
10
10
10
10
10
10
8-04
Time Out
Function
stop
2
2
2
2
2
2
2
2
2
2
2
14-00
Pattern [Avm] 60AVM
0
0
0
0
0
0
0
0
0
0
0
14-01
Switching
Frequency
4kHz
6
6
6
6
6
6
6
6
6
6
6
Содержание 09FC020
Страница 8: ...8 Fig 5 09FC 020 Unit Dimensions...
Страница 9: ...9 Fig 6 09FC 030 Unit Dimensions...
Страница 10: ...10 Fig 7 09FC 040 Unit Dimensions...
Страница 11: ...11 Fig 8 09FC 050 Unit Dimensions...
Страница 12: ...12 Fig 9 09FC 060 Unit Dimensions...
Страница 13: ...13 Fig 10 09FC 070 Unit Dimensions...
Страница 14: ...14 Fig 11 09FC 080 Unit Dimensions...
Страница 69: ......