50
Field Configuration
The following configurations must be set in the 09FC controls per
the site application for proper operation.
LEAVING WATER SETPOINT
OUTDOOR AIR SETPOINT
The Table 14 below is a reference for the major points in the con
-
trol. For a detailed list see appendix B.
Table 14 —
Field Configuration
POINT NAME
DESCRIPTION
DEFAULT/RANGE
Cool Enable
Enables or disables cooling operation.
D: Enable
R: Disable/Enable
Leaving Water Temp Setpoint
The leaving water temperature setpoint maintained by the module.
D: 44°F
R: 15 to 75°F
Outdoor Air Temp Setpoint
The outside air temperature below which the module is allowed to operate.
D: 50°F
R: –20 to 80°F
OAT Offset Setpoint
The number of degrees that the outdoor air temperature must rise above set-
point to disable the module’s operation.
D: 3°F
R: 1 to 10°F
Remote Contact Normal Logic
State
Specifies the remote contact’s normal logic state.
D: Open
R: Open/Closed
Fan VFD Run Status Normal Logic
State
Specifies the fan’s variable frequency drive run status normal logic state.
D: Open
R: Open/Closed
Fan VFD Output Type
Defines the type of fan variable frequency drive output control.
D: 0-10V
R: 0-10V/2-10V
Fan Initial Start Speed
The speed that the module’s fans are briefly run on initial startup.
D: 100%
R: 0 to 100%
Fan Minimum Speed
The lowest speed that the module’s fan is commanded when the fans’ vari
-
able frequency drive is enabled.
D: 20%
R: 0 to 100%
Fan Speed PID
The BACnet Object calculates the amount of fan speed required to satisfy the
Leaving Water Temp Setpoint
and allows access to the control loops tuning
parameters.
NOTE:
The following default values should be charged only by a technician
trained in tuning PID loop algorithms.
Action direct
Update Interval 1:00 mm:ss
Proportional 15
Integral 5
Derivative 0
Deadband 0
Bias 0
R: 0 to 100%
Bypass Valve PID
This BACnet Object calculates the amount of bypass required to satisfy the
Leaving Water Temp Setpoint when bypass valve modulation is enabled and
allows access to the control loop’s tuning parameter.
NOTE:
The following default values should be changed only by a technician
trained in turning PID Loop algorithms.
Action reverse
Update Interval 1:00 mm:ss
Proportional 10
Integral 2
Derivative 0
Deadband 0
Bias 0
R: 0 to 100%
Lvg Wtr Temp Setpoint OA Reset
Enables OA reset of the leaving water temperature’s setpoint.
D: Disable
R: Disable/Enable
Maximum LWT Setpoint OA Reset
The highest leaving water temperature setpoint reset allowed by the outdoor
air temperature.
D: 10°F
R: 0 to 25°F
Содержание 09FC020
Страница 8: ...8 Fig 5 09FC 020 Unit Dimensions...
Страница 9: ...9 Fig 6 09FC 030 Unit Dimensions...
Страница 10: ...10 Fig 7 09FC 040 Unit Dimensions...
Страница 11: ...11 Fig 8 09FC 050 Unit Dimensions...
Страница 12: ...12 Fig 9 09FC 060 Unit Dimensions...
Страница 13: ...13 Fig 10 09FC 070 Unit Dimensions...
Страница 14: ...14 Fig 11 09FC 080 Unit Dimensions...
Страница 69: ......