21
Fig. 21 —
09FC 050-080 Parallel Piping
30XV 200, 250-500 Standard Tier
160-500 Mid Tier
140-500 High Tier
Fig. 22 —
Modular Unit Series Piping
Step 4 —
Fill the Chilled Water Loop
WATER SYSTEM CLEANING
Proper water system cleaning is of vital importance. Excessive
particulates in the water system can cause excessive pump seal
wear, reduce or stop flow, and cause damage of other components.
Water quality should be maintained per recommendations in the
chiller installation manual. This may vary for different types of
chillers. Failure to maintain proper water quality may result in heat
exchanger failure.
1. Install a temporary bypass around the unit to avoid circulating
dirty water and particulates into coils during the flush. Use a
temporary circulating pump during the cleaning process.
09FC Unit
LWT
(Note 2)
EWT
(Note 2)
09FC
Control
Panel
NOTES:
1. Allow 36 in. for fan VFD access. Verify 36 in. meets local codes.
2. EWT and LWT thermistors must be installed in the field.
Thermistors are supplied inside control panel. Add 1/4 in. NPT hole in pipe for mounting.
LWT thermistor well must be in mixed flow piping.
3. Chiller tube service must be done from control panel end for this arrangement. See chiller
certified drawings for details.
Chiller
36"
(Note 1)
Check Valve
Service Valve
Leaving Water
Connection
Bypass Valve
Bypass Valve
Actuator
Bypass Line
Coil Leaving
Water Manifold
Coil Entering
Water Manifold
¼” NPT Drain
¼” NPT Drain
Entering Water
Connection
CAUTION
Failure to properly clean all piping and components of the
chilled water system before unit start-up may result in
plugging of the heat exchanger, which can lead to poor
performance, nuisance alarms and damage from freezing.
Freezing damage caused by an improperly cleaned system
represents abuse and may impair or otherwise negatively affect
the Carrier product warranty.
Содержание 09FC020
Страница 8: ...8 Fig 5 09FC 020 Unit Dimensions...
Страница 9: ...9 Fig 6 09FC 030 Unit Dimensions...
Страница 10: ...10 Fig 7 09FC 040 Unit Dimensions...
Страница 11: ...11 Fig 8 09FC 050 Unit Dimensions...
Страница 12: ...12 Fig 9 09FC 060 Unit Dimensions...
Страница 13: ...13 Fig 10 09FC 070 Unit Dimensions...
Страница 14: ...14 Fig 11 09FC 080 Unit Dimensions...
Страница 69: ......