8.5 Variables accessible via serial
connection – driver B
Description
Default
Min
Max
Type
CAREL SVP Modbus®
R/W
Valve opening
0
0
100
A
66
65
R
Control set point
0
-60 (-870)
200 (2900)
A
67
66
R
Superheat
0
-40 (-72)
180 (324)
A
68
67
R
Suction temperature
0
-85 (-121)
200 (392)
A
69
68
R
Evaporation temperature
0
-85 (-121)
200 (392)
A
70
69
R
Evaporation pressure
0
-20 (-290)
200 (2900)
A
71
70
R
EPR pressure (back pressure)
0
-20 (-290)
200 (2900)
A
72
71
R
Hot gas bypass pressure
0
-20 (-290)
200 (2900)
A
73
72
R
Hot gas bypass temperature
0
-85 (-121)
200 (392)
A
74
73
R
CO
2
gas cooler outlet temperature
0
-85 (-121)
200 (392)
A
75
74
R
CO
2
gas cooler outlet pressure
0
-20 (-290)
200 (2900)
A
76
75
R
CO
2
gas cooler pressure set point
0
-20 (-290)
200 (2900)
A
77
76
R
4 to 20 mA input value (S3)
4
4
20
A
78
77
R
MOP: suction temperature threshold (S4)
30
-85 (-121)
200 (392)
A
103
102
R/W
Liquid regulation evaporator/ condenser level percentage
0
0
100
A
117
116
R
Valve position
0
0
9999
I
49
176
R
Current unit cooling capacity
0
0
100
I
50
177
R/W
EVD status
0
0
20
I
51
178
R
Protector status
0
0
5
I
52
179
R
Control mode
1
1
26
I
73
200
R/W
Adaptive control status
0
0
6
I
77
204
R
Last tuning result
0
0
8
I
78
205
R
Extended measured probe S3 (*)
0
-2000 (-2901)
20000 (29007)
I
84
211
R
Start control delay
6
0
18000
I
87
214
R/W
Emergency closing speed valve
150
1
2000
I
86
215
R/W
Valve opening position % in standby
0
0
100
I
92
219
R/W
ALARMS
LowSH (low superheat)
0
0
1
D
26
25
R
LOP (low evaporation temperature)
0
0
1
D
27
26
R
MOP (high evaporation temperature)
0
0
1
D
28
27
R
Low suction temperature
0
0
1
D
29
28
R
EEV motor error
0
0
1
D
30
29
R
Status of relay
0
0
1
D
31
30
R
ALARMS
Adaptive control ineffective
0
0
1
D
42
41
R
Value backup digital input
0
0
1
D
48
47
R/W
LowSH protection status
0
0
1
D
54
53
R
LOP protection status
0
0
1
D
55
54
R
MOP protection status
0
0
1
D
56
55
R
Direct relay control
0
0
1
D
61
60
R/W
Tab. 8.d
(*) The displayed variable is to be divided by 100, and allows us to appreciate
the hundredth of a bar (psig).
Type of variable: A= analogue; D= digital; I= integer
SVP= variable address with CAREL protocol on 485 serial card.
Modbus®: variable address with Modbus® protocol on 485 serial card.