ENG
“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
27
Note: the control error is the result of the difference between the set
point and the measurement:
setpoint
error
PID
measure
Direct operation: error = measurement - set point
Reverse operation: error = set point - measurement
P
rogrammable control configuration
Important: for the explanation of the HiTcond (high condensing
temperature), reverse HiTcond protectors and the “Modulating thermostat”
auxiliary control function, see Appendix 2.
Each digit in the “Programmable control configuration” parameter has a
special meaning, depending on its position:
POSITION
DESCRIPTION
NOTE
Tens of thousands (DM) Control: direct/reverse
Select type of control
action: direct/reverse
Thousands (M)
Auxiliary control
Selection any auxiliary
control or protector
used for superheat
control
Hundreds
Do not select
-
Tens
Controlled value
Select the type of
controlled physical
value (temperature,
pressure…)
Units
Measurement function
Select the function for
calculating the value
controlled by the PID
(measurement)
Tab. 5.a
Direct/reverse control – Tens of thousands
Value
Description
0
PID in direct control
1
PID in reverse control
2,….9
-
AUX control - Thousands
Value
Description
0
None
1
HITCond protection
2
Modulating thermostat
3
HiTcond protection in reverse
4,….9
-
Hundreds
– DO NOT SELECT
Controlled value - Tens
Value
Description
0
Temperature (°C/°F), absolute
1
Temperature (K/°F), relative
2
Pressure (bar/psi), absolute
3
Pressure (barg/psig), relative
4
Current (mA) for control
5
Voltage (V) for control
6
Voltage (V) for positioner
7
Current (mA) for positioner
8.9
-
Measurement function - Units
Value
Description
0
f1(S1)+ f2(S2)+ f3(S3)+ f4(S4)
1,….9
-
P
rogrammable control input
The function assigned to each input is defined by parameter - “Programmable
control input”. The parameter has 16 bits and is divided into 4 digits, as
described in “Programmable control configuration”, corresponding to the 4
probes, S1, S2, S3, S4.
POSITION
DESCRIPTION
Thousands
Function of probe S1
Hundreds
Function of probe S2
Tens
Function of probe S3
Units
Function of probe S4
Value
Input function
0
0
1
+ Sn
2
- Sn
3
+ Tdew (Sn)(*)
4
- Tdew (Sn)
5
+ Tbub (Sn)(**)
6
- Tbub (Sn)
7,8,9
-
(*): Tdew() = function for calculating the saturated evaporation temperature
according to the type of gas.
(**): Tbubble = function for calculating the condensing temperature.
B
C
Enthalpy [kJ/kg]
Pr
es
su
re [
M
Pa]
A
D
E
F
Fig. 5.o
Key:
TA
Saturated evaporation temperature = Tdew
TB
Superheated gas temperature = suction temperature
TB – TA Superheat
TD
Condensing temperature (Tbubble)
TE
Subcooled gas temperature
TD – TE Subcooling
O
ptions/ programmable control set point
Note:
-
if Control = Programmable special control, the setting of the
“Programmable control options” parameter has no affect;
-
if Control = “Programmable positioner”, the settings of the “Programmable
control options” and “Programmable control set point” parameters have
no affect.
The physical value measured is assigned to the individual probes S1 to S4 by
the “Programmable control options” parameter. The parameter has 16 bits and
is divided into 4 digits, as described in “Programmable control configuration”,
corresponding to the 4 probes, S1, S2, S3, S4. The control set point si sets to
the “Programmable control set point” parameter.
POSITION
DESCRIPTION
Thousands
Function of probe S1
Hundreds
Function of probe S2
Tens
Function of probe S3
Units
Function of probe S4
Value
Input function
0
None
1
Suction temperature
2
Evaporation pressure
3
Evaporation temperature
4
Condensing pressure
5
Condensing temperature
6
Temperature (modulating thermostat)
7,8,9
-