![Carel EVD Evolution Twin Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/carel/evd-evolution-twin/evd-evolution-twin_user-manual_2557374014.webp)
ENG
“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
14
3. USER
INTERFACE
The user interface consists of 8 LEDs that display the operating status, as
shown in the table:
VBA
T
G0
G
E
X
V connection
Power Supply
Relay
NO 1
COM 1
4
2
3
1
GND
V REF
S1
S2
S3
S4
DI1
DI2
Analog – Digital Input
Network
GND
Tx/Rx
EVD
evolution
twin
Fig. 3.a
Key:
LED
On
Off
Flashing
NET
Connection active
No
connection
Communication error
OPEN A/B Opening valve A/B
-
Driver A/B disabled (*)
CLOSE A/B Closing valve A/B
-
Driver A/B disabled (*)
OPEN B/
CLOSE B
-
-
EVD Evolution TWIN
operating as single
driver
A
/
B
Active alarm driver A/B
-
-
Controller powered
Controller off
Wrong power supply
(see chap. on Alarms)
Tab. 3.a
(*) Awaiting completion of the initial configuration
3.1 Assembling the display board (accessory)
The display board, once installed, is used to perform all the configuration and
programming operations on the two drivers. It displays the operating status,
the significant values for the type of control that the drivers are performing
(e.g. superheat control), the alarms, the status of the digital inputs and the
relay outputs. Finally, it can save the configuration parameters for one
controller and transfer them to a second controller (see the procedure for
uploading and downloading the parameters).
For installation:
•
remove the cover, pressing on the fastening points;
•
fit the display board, as shown;
•
the display will come on, and if the controller is being commissioned, the
guided configuration procedure will start.
press
press
Fig. 3.b
Important:
the controller is not activated if the configuration
procedure has not been completed.
The front panel now holds the display and the keypad, made up of 6 buttons,
that, pressed alone or in combination, are used to perform all the configuration
and programming operations on the controller.
3.2 Display and keypad
The graphic display shows two variables for each driver (A, B), the control
status of the driver, activation of the protectors, any alarms and the status of
the relay output.
Surriscaldam.
4.9 K
Apertura
valvola
44 %
ON
MOP
ALARM
-- Rele
1
2
3
4
5
7
A/B
6
T
8
Fig. 3.c
Key:
1
variable 1 on the display (driver A/B)
2
variable 2 on the display (driver A/B)
3
relay status (driver A/B)
4
alarm (press “HELP”)
5
protector activated
6
control status
7
current display: driver A/driver B
8
adaptive control in progress
Messages on the display
Control status
Active protection
ON
Operation
LowSH
Low superheat
OFF
Standby LOP
Low
evaporation
temperature
POS
Positioning
MOP
High evaporation
temperature
WAIT Wait
HiTcond
High
condensing
temperature
CLOSE
Closing
INIT
Valve motor error recognition
procedure (*)
TUN
Tuning in progress
Tab. 3.b
(*) The valve motor error recognition procedure can be disabled. See
paragraph 9.5.
(**) Only if EVD Evolution TWIN is operating as a single driver or programmable
superheat control is enabled.
Keypad
Button
Function
Prg
•
opens the screen for entering the password to access
programming mode.
•
if in alarm status, displays the alarm queue;
•
in the “Manufacturer” level, when scrolling the parameters,
shows the explanation screens (Help);
•
pressed together with ENTER, switches the display from one
driver to the other
Esc
•
exits the Programming (Service/Manufacturer) and Display
modes;
•
after setting a parameter, exits without saving the changes.
UP/DOWN
•
navigates the screens on the display;
•
increases/decreases the value.
ENTER
•
switches from display to parameter programming mode;
•
confirms the value and returns to the list of parameters;
•
pressed together with HELP, switches the display from one
driver to the other.
Tab. 3.c
Note: :
the variables displayed as standard can be selected by
configuring the parameters “Variable 1 on display” and “Variable 2 on display”
for each driver. See the list of parameters.