MAP1
Page 18 of 31
Installation Manual
June 2018 • Rev. 1.6
The MAP1 can be provisioned for
all I/O
which allows for 8 input points and 8
output points to be used and no door combination.
The inputs can be individually set through the host software to be supervised or non-
supervised. The default input setting is non-supervised. Supervised input points require
a Cansec CA-EOL resistor pack to be placed at the device being monitored. Supervised
input points will inform the host of 4 supervised states:
Alarm
,
Secure
,
Trouble High
and
Trouble Low
These are the same 8 input points which can be used with the door provisioning
combinations, thus devices such as the Door Contact and RTE/REX pushbutton can
used in supervised mode of operation if necessary.
Input Wiring – Supervised or Non-Supervised
Figure 11