13.
If no error file is present, it’s recommended that the file MAPCFG.txt
be reviewed to ensure that the line
<USB INIT DONE>
has
been written by the MAP1 controller indicating that the IP configuration has been
successfully saved and initialized.
14.
A file named SysInf.txt is also present. This file contains critical information if
debugging is required. If this file is not present it is recommended that the
controller be updated with the latest firmware.
FORCED ENTRY OUTPUT
To monitor forced-entry or door-held-open alarm conditions, connect a Normally
Closed door contact switch or sensor to the door contact input. The (
MF
)
multifunction relay, when configured as
Forced Entry
,
will be activated if the door is
forced open without either an access-granted or an exit-button event. A message will be
transmitted to the host software if the panel is online.
DOOR HELD OPEN OUTPUT
The (
MF
) multifunction relay, when configured as
Door Held Open
,
will be activated
if the lock is unlocked and the door is held open longer than the permitted door-held-
open time programmed from the host software. The reader beeps to notify the user by
first generating a pre-alert beep followed by a solid beep, then a message is also
transmitted to the host software if the panel is online.
ALARM SHUNT OUTPUT
The (
MF
) multifunction relay is factory configured as
Alarm Shunt
. When an access-
granted or an exit button event occurs, the alarm shunt output relay is activated first
followed by the lock output relay. The relay can be used to bypass an external alarm
point. When an access-granted or an exit button event is complete, the lock output is
turned off followed by the Alarm Shunt output after a short delay. If a door contact is
used then Alarm Shunt output is turned off shortly after the door contact is closed.
Содержание MAP1
Страница 1: ...MAP1 Controller INSTALLATION MANUAL June 2018...
Страница 7: ...MAP1 Page 7 of 31 Installation Manual June 2018 Rev 1 6 MAP1 Controller Layout Figure 1...
Страница 13: ...MAP1 Page 13 of 31 Installation Manual June 2018 Rev 1 6 Figure 6 Non Supervised...
Страница 14: ...MAP1 Page 14 of 31 Installation Manual June 2018 Rev 1 6 Figure 7 Supervised...
Страница 17: ...MAP1 Page 17 of 31 Installation Manual June 2018 Rev 1 6 INPUT AND OUTPUT POINT WIRING General Layout Figure 10...